E93.1601EN032.C VGH installation manual
86
13 TEMPERATURE
PROTECTION
The difference between Supply temperature and Return Temperature is continuously monitored. A too big
difference can indicate a defective pump or a clogged heat exchanger. To protect the boiler, the burner controller
reduces the input when the temperature difference
∆
T becomes too high:
At maximum boiler input
∆
T is limited to 63 °F (35 °C) (Hx_Diff_DeltaT_Min).
In between 63 °F (35 °C) and 77 °F (43 °C) boiler input modulates between minimum and maximum.
At minimum boiler input
∆
T above 77 °F (43 °C) is allowed (Hx_Diff_DeltaT_Min
plus 14
°F (+8 °C)).
Above
∆
T = 86 °F (48 °C), the boiler is switched OFF during HX_Diff_Max_Wait_Time.
Relevant factory set variables
Parameter
Level
Factory Setting. Range
HX Diff DeltaT Min
3: Factory 63 ºF (35 ºC)
18….144 ºF (10 ….80 ºC)
HX Diff Max Wait Time
Wait time after upper limit primary heat exchanger differential has been exceeded.
3: Factory 180 Sec.
1….255 Sec.
14
ERROR
INFORMATION.
Errors can be divided in three groups:
• Manual reset locking errors (can only be reset by the reset button).
• Blocking errors (will disappear when error is gone)
• Warnings (will disappear when the warning is gone, not stored in the
BCU
)
The boiler circulator will continue to run during most locking and blocking error codes
. This is to prevent the
freezing of the Central Heating circuit when the boiler is in error during the winter period. For some non-volatile
lockouts the circulator will not be running, also see the error tables in this chapter for more details.
Boiler history.
The last 15 lockouts and 15 blocking errors are stored in the boiler control. This boiler history can be shown via the
Boiler History screen via the installer boiler status menu in one of the advanced displays.
Successful
ignitions
Failed
Ignitions
Flame
Failures
Operation
days
CH Burner Hours
DHW
Burner
Hours
Table 13. 1
Figure 13. 2
63
77
86
0
20
40
60
80
100
120
50
60
70
80
90
100
b
o
ile
r
in
put
[%
]
delta
T
[°F]
boiler
input
control
high
power
low
power
off
Summary of Contents for VGH-299-CH
Page 6: ...E93 1601EN032 C VGH installation manual 6 1 SAFETY GUIDELINES ...
Page 59: ...E93 1601EN032 C VGH installation manual 59 Ladder Logic Diagram Figure 11 3 ...
Page 60: ...E93 1601EN032 C VGH installation manual 60 Electrical schematics Figure 11 4 ...
Page 61: ...E93 1601EN032 C VGH installation manual 61 Figure 11 5 ...
Page 123: ...E93 1601EN032 C VGH installation manual 123 22 SPARE PARTS Figure 22 1 ...
Page 124: ...E93 1601EN032 C VGH installation manual 124 Figure 22 2 ...
Page 127: ...E93 1601EN032 C VGH installation manual 127 ...