E93.1601EN032.C VGH installation manual
75
12.8.5
C
ENTRAL
H
EATING WITH ANALOG INPUT CONTROL OF SETPOINT
;
CH
MODE
4
CH mode is set to 4. In this mode of operation, the boiler CH setpoint is controlled by an analog input signal
provided by a remote means such as a Building Management System or a system controller. The analog input 0-
10 Vdc is used to adjust the boiler setpoint between the CH_Setpoint_Min and the CH_Setpoint_Max settings.
The minimum analog input signal will correspond to the CH_Setpoint_Min parameter and the maximum analog
input signal will correspond to the CH setpoint maximum parameter. All other safety and control functions
associated with the boiler will react normally to adverse condition and override control of the analog signal to
prevent an upset condition. This means for example that when signal is going up faster than the boiler can regulate
that the boiler will slow down to prevent overshoot in temperature.
The CH_Setpoint_Min and CH_Setpoint_Max parameters can be adjusted to provide the desired temperature
adjustment band. A heat request will be generated by an input of 1.5 volts or higher. The setpoint modulation will
occur between 2 and 9 volts. The request for heat will be removed when the voltage drops below 1 volt.
RT input must be shorted to generate heat demand. / Min/Max CH power setting is limiting 0-10V range.
Figure 12. 4
Parameters
Level
(Default) Value
Settable
CH_Mode
2: Installer
0
Mode 0, 1, 2, 3, 4, 5
CH_Setpoint_Minimum
2: Installer
68 ºF (20 ºC)
68...194 ºF (20...90 ºC)
CH_Setpoint_Maximum
2: Installer
194 ºF (90 ºC)
68...194 ºF (20...90 ºC)
Table 12. 16
Summary of Contents for VGH-299-CH
Page 6: ...E93 1601EN032 C VGH installation manual 6 1 SAFETY GUIDELINES ...
Page 59: ...E93 1601EN032 C VGH installation manual 59 Ladder Logic Diagram Figure 11 3 ...
Page 60: ...E93 1601EN032 C VGH installation manual 60 Electrical schematics Figure 11 4 ...
Page 61: ...E93 1601EN032 C VGH installation manual 61 Figure 11 5 ...
Page 123: ...E93 1601EN032 C VGH installation manual 123 22 SPARE PARTS Figure 22 1 ...
Page 124: ...E93 1601EN032 C VGH installation manual 124 Figure 22 2 ...
Page 127: ...E93 1601EN032 C VGH installation manual 127 ...