code
Error
Description
Cause
Solving
33
LWCO_1_
ERROR
Low water cut off 1 error
There is no water in
the heat exchanger
or not electrically
connected
Check if there is enough
water in the heat exchanger
if not so fill up the system
34
LWCO_2_
ERROR
Low water cut off 2 error
There is no water in
the heat exchanger
or not electrically
connected
Check if there is enough
water in the heat exchanger
if not so fill up the system
35 APS_NOT_CLO
SED_IN_POST_
PURGE
Air pressure switch not
closing during post-purge
1
no air transport to
the burner after
heat demand; flue
or air inlet is
blocked or APS is
jammed or air
signal hose not
connected to the air
intake pipe or water
in hose
Check if there are any
obstructions in the flue or air
intake, replace APS if
jammed, connect air hose to
the air intake pipe, remove
any water from the hose.
36
GAS_PRESSUR
E_ERROR
Gas pressure switch open
for more than
E2_GPS_Timeout
wrong gas pressure
on gas supply
Check if gas pressure is in
limits of the gas pressure
switch.
Table 14. 1
Summary of Contents for VGH-299-CH
Page 6: ...E93 1601EN032 C VGH installation manual 6 1 SAFETY GUIDELINES ...
Page 59: ...E93 1601EN032 C VGH installation manual 59 Ladder Logic Diagram Figure 11 3 ...
Page 60: ...E93 1601EN032 C VGH installation manual 60 Electrical schematics Figure 11 4 ...
Page 61: ...E93 1601EN032 C VGH installation manual 61 Figure 11 5 ...
Page 123: ...E93 1601EN032 C VGH installation manual 123 22 SPARE PARTS Figure 22 1 ...
Page 124: ...E93 1601EN032 C VGH installation manual 124 Figure 22 2 ...
Page 127: ...E93 1601EN032 C VGH installation manual 127 ...