E93.1601EN032.C VGH installation manual
74
12.8.3
CH
WITH CONSTANT CIRCULATION SYSTEM OUTDOOR RESET
;
CH
MODE
2
When CH_Mode is set to 2, full weather compensator is chosen. For this mode an outdoor sensor has to be
connected. The CH_Setpoint is calculated on the same way as described in § 12.7.2.
However, the demand does not depend on the Room Thermostat input but on the outdoor temperature and the
outdoor reset setpoint. When the outdoor temperature is below Warm_Weather_Shutdown (settable) CH demand
is created.
During the night an input signal from an external clock can lower the CH_Setpoint. When the RT input opens
CH_Setpoint will be decreased with Night_Setback_Temp. The RT input does not influence the CH demand
directly!
This can be done by connecting a relay contact or clock thermostat to terminal 12 and 13 on the low voltage
connectors of the boiler.
The room thermostat is only being used in this function to switch between a night
setback temperature and a daytime temperature, there is always a constant demand for heat in CH mode 2.
The Night Setback temperature can be set by using the installer password and changing parameter 28 in the boiler
parameters, default value is setpoint - 50 °F.
Boiler Parameters
(25) Warm Weather Shutdn 72 °F
▲
(26) Boost Temp increment
0
°F
(27) Boost Time Delay 20 min
(28) Night Setback Temp
. 7 °F
▼
Adjustable constant Circulation Parameters
Parameters
Level
(Default) Value
Settable
CH_Mode
2: Installer
0
Mode 0 - 5
Warm_Weather_Shutdown
Set max. outdoor temp.
Above this temperature heat demand is blocked.
2: installer
72 ºF (22 ºC)
32...95 ºF (0...35 ºC)
CH_Setpoint_Diff
Adjusts the calculated CH setpoint.
1: User
0 ºF (0 ºC)
-18...+18 ºF (-10...+10 ºC)
12.8.4
CH
WITH CONSTANT CIRCULATION AND PERMANENT HEAT DEMAND
;
CH
MODE
3
For this mode the CH_ Mode must be set to 3, no outdoor sensor is needed. The supply temperature is kept
constantly at the setpoint temperature. The boiler is controlled in a similar way as described in paragraph 12.7.1.
When the room thermostat contact opens CH_Setpoint will be decreased with Night_Setback_Temp. In this
condition the circulator is always ON.
Please note that the circulator starts every 24 hours function is not performed during this mode. In this mode the
circulator will be running continuously.
Picture 12.15
Table 12. 14
Parameters
Level
(Default) Value
Settable
CH_Mode
2: Installer
0
Mode 0 - 5
CH_Setpoint
2: Installer
176 ºF (80 ºC)
68…..194 ºF (20…..90 ºC)
Table 12. 15
Summary of Contents for VGH-299-CH
Page 6: ...E93 1601EN032 C VGH installation manual 6 1 SAFETY GUIDELINES ...
Page 59: ...E93 1601EN032 C VGH installation manual 59 Ladder Logic Diagram Figure 11 3 ...
Page 60: ...E93 1601EN032 C VGH installation manual 60 Electrical schematics Figure 11 4 ...
Page 61: ...E93 1601EN032 C VGH installation manual 61 Figure 11 5 ...
Page 123: ...E93 1601EN032 C VGH installation manual 123 22 SPARE PARTS Figure 22 1 ...
Page 124: ...E93 1601EN032 C VGH installation manual 124 Figure 22 2 ...
Page 127: ...E93 1601EN032 C VGH installation manual 127 ...