E93.1601EN032.C VGH installation manual
77
Demand for Domestic Hot Water
12.9.1
N
O
D
OMESTIC
H
OT
W
ATER
;
DHW
MODE
0
No domestic hot water is available. The T_DHW_Out sensor does not need to be connected.
12.9.2
DHW
S
TORAGE WITH SENSOR
;
DHW
MODE
1
Mode 1: DHW is prepared by warming up a store. Either a DHW circulator or 3-way valve can be used to switch
to DHW mode.
The DHW temperature in the tank is measured with sensor T_Store and set with parameter DHW_Store_Setpoint.
When this sensor drops below DHW_Store_Setpoint
minus
DHW_Store_Hyst_Down the control detects a
demand for the store and starts the general and DHW circulator.
If the supply temperature T_Supply is below
DHW_Store_Setpoint
plus
DHW_Store_Supply_Extra
minus
DHW_Supp_Hyst_Down the boiler is started as well.
When the boiler is ON, the power is PID-modulated so T_Supply is regulated towards
DHW_Setpoint
plus
DHW_Store_Supply_Extra.
The boiler is stopped when the supply temperature rises above
DHW_Store_Setpoint
plus
DHW_Store_Supply_Extra
plus
DHW_Supp_Hyst_Up.
The demand for the tank is ended when the tank-sensor rises above
DHW_Store_Setpoint
plus
DHW_Store_Hyst_Up. The circulator continues DHW_Post_Pump_Period.
DHW Priority
Standard DHW demand has priority over CH demand but the priority period is limited up to
DHW_Max_Priority_Time. The priority timer starts when both CH and DHW demand are present. After the
DHW_Max_Priority_Time is achieved, the control will switch from DHW to CH operation. CH has priority now for
a maximum period of DHW_Max_Priority_Time.
Different DHW Priority types can be chosen:
DHW priority
Description
0
Time
DHW has priority to CH during
DHW_Max_Priority_Time
1
OFF
CH always has priority to DHW
2
ON
DHW always has priority to CH
Default
DHW_Priority
is set to 2.
Store warm hold function
Because of the presence of the indirect tank sensor (
T_Store
) the control can detect demand for holding the indirect
tank hot.
If T_Store drops below DHW_Store_Setpoint
minus
DHW_Store_Hold_Warm the boiler starts at minimum power.
The boiler stops if T_Store is higher than DHW_Store_Setpoint
plus
DHW_Store_Hyst_Up.
Relevant variables
Specific Parameters
Level
(Default) Value
Range
DHW_Mode
2: Installer
5 ???
0, 1, 2, 3, 5, 6, 7, 8
DHW_Store_Setpoint
Sets the desired DHW temperature.
1: User
149
ºF (
65
ºC)
104...160
ºF (40...71 ºC)
DHW_Store_Supply_Extra
Increases the supply temperature to the store until
DHW_Store_Setpoint
+
DHW_Store_Supply_Extra.
2: Installer
27
ºF (15 ºC)
0...54
ºF (0...30 ºC)
Status Variables
Value
DHW control state
Central Heating controller state
0
Idle
1
Request
2
Demand
3
Post circulation
4
Off
Table 12. 18
Table 12. 19
Table 12. 20
Summary of Contents for VGH-299-CH
Page 6: ...E93 1601EN032 C VGH installation manual 6 1 SAFETY GUIDELINES ...
Page 59: ...E93 1601EN032 C VGH installation manual 59 Ladder Logic Diagram Figure 11 3 ...
Page 60: ...E93 1601EN032 C VGH installation manual 60 Electrical schematics Figure 11 4 ...
Page 61: ...E93 1601EN032 C VGH installation manual 61 Figure 11 5 ...
Page 123: ...E93 1601EN032 C VGH installation manual 123 22 SPARE PARTS Figure 22 1 ...
Page 124: ...E93 1601EN032 C VGH installation manual 124 Figure 22 2 ...
Page 127: ...E93 1601EN032 C VGH installation manual 127 ...