When there is a strong external interference, in order to prevent external interference, you can set the filter time for the DI terminal. Its meaning
is that the signal of the DI terminal must maintain the time more than the P6-00 setting time and will be recognized as the valid signal by drive.
For example, P6-00 is set to 2, the signal of the DI terminal must maintain the 2ms will be recognized as effective by drive.
P6-01
DI Level logic
Initail value
Unit
Communication
Address
00000000
-
2601H
Control Mode
:
P S T
Range
:
00000000
~
11111111
Data size
:
16bit
Display mode
:
Binary system
Parameter function
:
Set the level logic of each DI terminal, stop setting after motor stops and re-power effective.
0 0 0 0 0 0 0 0
DI8 DI7 DI6 DI5 DI4 DI3 DI2 DI1
8 loads way DI can be set, for a certain, bit=0, the external input low effective; if bit=1, then the external input high effective.
2ms
2ms
2ms
Actual DI
level
2ms
2ms
Low level effective
High level
effective
P6-01=1
P6-01=0
DI effective
DI effective
DI Invalid
DI Invalid
DI effective
Figure7-21 DI Terminal filter and level
P6-02
DI1
function code
Initail value
Unit
Communication
Address
1
-
2602H
P6-03
DI2
function code
Initail value
Unit
Communication
Address
2
-
2603H
P6-04
DI3
function code
Initail value
Unit
Communication
Address
3
-
2604H
P6-05
DI4
function code
Initail value
Unit
Communication
Address
4
-
2605H
P6-06
DI5
function code
Initail value
Unit
Communication
Address
5
-
2606H
P6-07
DI6
function code
Initail value
Unit
Communication
Address
6
-
2607H
P6-08
DI7
function code
Initail value
Unit
Communication
Address
7
-
2608H
P6-09
DI8
function code
Initail value
Unit
Communication
Address
8
-
2609H
Control Mode
:
P S T
Range
:
0
~
99
Data size
:
16bit
Display mode
:
Decimal system
Parameter function
:
Set the function of the DI1~DI8 terminal, refer to table 7-5. Stop setting after motor stops and re-power effective.
External 8 DI corresponding function settings, can be set to a range of 0~99, but the current part of the retention items.
As any DI to set the function code, the corresponding DI is valid, the selected event occurs. Such as P6-02=1, the DI1 is set to serve as the