FAN Fault Conditions
This equation sets the amber LED (fault) to ON when the fan control relay is set to operate
the fan but the airflow indicator does not report that air is flowing, when the fan control relay
is set to stop the fan but the airflow indicator reports that air is flowing or a fault signal is
received from the Mechanical Services Board.
[INPUTS]
STATUS
ON
M1
-
5
-
1
| MRELAY | RELAY | FAN 1 START RELAY
AND
NOT
STATUS
ON
M1
-
5
-
2
| MTSENSE | UTILITY | FAN 1 RUN INDICATION
SAVE
1
STATUS
ON
M1
-
3
-
0
| RIAM | RELAY | FAN 1 STOP RELAY
AND
STATUS
ON
M1
-
5
-
2
| MTSENSE | UTILITY | FAN 1 RUN INDICATION
OR
RECALL
1
DELAY
ANALOG
A278 | Analog Timer | ANALOG | TIMER | FAN FAULT DELAY - FAN 1
A260 | Analog Timer SetPoint | ANALOG | ANALOG | FAN FAULT DELAY SETPOINT
OR
STATUS
ON
M1
-
7
-
2
| MINPUT | TROUBLE | FAN MECH BOARD FAULT
[END INPUTS]
[OUTPUTS]
TRACK
ON
PRI
=
9
,
9
P1265 | DIGITAL | TROUBLE | FAN #1 FAULT
[END OUTPUTS]
Summary of Contents for 4100ES-S1
Page 1: ...4100ES S1 Fire Indicator Panel Programming Guide Australian Programming Guide LT0400 Issue 1 5...
Page 2: ......
Page 7: ...Document LT0400 4100ES S1 Programming Guide Introduction 1 1 1 Introduction...
Page 10: ...4100ES S1 Programming Guide Document LT0400 Introduction 1 4 THIS PAGE IS INTENTIONALLY BLANK...
Page 11: ...Document LT0400 4100ES S1 Programming Guide System Overview 2 1 2 System Overview...
Page 39: ...Document LT0400 4100ES S1 Programming Guide Adding Zone Displays 7 1 7 Adding Zone Displays...
Page 61: ...Document LT0400 4100ES S1 Programming Guide Custom Control 9 1 9 Custom Control...
Page 69: ...Document LT0400 4100ES S1 Programming Guide AS1668 Fan Controls 10 1 10 AS1668 Fan Controls...
Page 95: ...Document LT0400 4100ES S1 Programming Guide Appendices 12 1 12 Appendices...