4100ES-S1 Programming Guide
Document: LT0400
Custom Control
9-4
9.3
Creating a New Equation
9.3.1
Select User Program
The first step in defining a new Custom Control equation is to add the equation to one of the
five User Programs -- Program 3 through Program 7. It is recommended that Program 6 is
used for general functions and Program 7 is used for AS1668 Fan Controls. Follow these
steps to do this.
1. Right click on one of the user programs (Program 3 through Program 7), located at the
bottom of the program list, and select
Add Equation…
from the list of options.
2. The properties dialog shown below appears. Enter a name for the equation in the
Label:
text box and click on
OK
.
The Equations section of the Custom Control window updates to include the
[INPUTS],
[END INPUTS]
, etc entries.