4100ES-S1 Programming Guide
Document: LT0400
Creating a Configuration
4-2
4.1
Creating a New Project File
This method describes how to create a new 4100ES-S1 configuration using the template
configuration file as the starting point. SF0459 contains the zipped template files. These files
should be unzipped to an appropriate folder on your PC such as C:\4100ES-S1JOBS. Run
the ES programmer of the correct version and click on the ‘File’ menu and select ‘Open’.
Browse to the location containing the 5 default configurations supplied with SF0459:
S1_16ZN.SDB4100U for 16 zones,
S1_32ZN.SDB4100U for 32 zones
S1_64ZN.SDB4100U for 64 zones.
S1_16Z_F.SDB4100U for 16 zones, 8 fans
S1_32Z_F.SDB4100U for 32 zones, 12 fans
Choose the one that has more front panel zones than are required, as it is easier to remove
extra zones than to add more. Click OK.
All templates have the required Pseudo points and Custom Control equations for fan
controls. The templates with _F also have hardware preconfigured.
After the file is opened do a ‘
Save As
’/’
Copy
...’, enter the new job name and click OK. Note
that the ‘Job Name’ you enter will show on the front panel when the “
Display Software
Revision Level
” command is entered.
Now proceed with adding and modifying the site specific information as described below.
4.2
Adding Panel Information
Enter the
relevant information on the ‘General Info’ page in the ‘Panel’ tab.
Panel Information
o
Description = Site name.
o
Alternate Description = Site name.
o
Project Number = Software job number (must be obtained from TFPP/Simplex).
o
Order number = Client’s order # for the panel.
o
Agency listing = should always be - CSIRO.
o
NFPA Standard = (not required).
o
Standby Generator = unticked.
o
Hours of standby battery = should be 24, or 72 if not brigade connected.
o
A/C breaker location = (fill in if known).
Branch Information
o
Branch number = (not required).
o
Branch location = Local Simplex office location.
o
Contact = Local Simplex contact name (could be sales person or tech etc).
o
Sales person = Local Simplex sales person’s name.
o
Project Eng = Name of project engineer (system designer).
o
Technician = Service technician’s name (if known).
o
Customer = Building owner (if known).
o
Contractor = Contractor company name.
Programmed by - Appropriate fields to be filled in, i.e., if programmed by TFPP/Simplex,
they will fill in branch name file and phone. If programmed by contractor, put in local
TFPP/Simplex contact name (e.g., sales rep).
Hardware lock enable = leave unchecked.
Comment = Further information like panel location.
Summary of Contents for 4100ES-S1
Page 1: ...4100ES S1 Fire Indicator Panel Programming Guide Australian Programming Guide LT0400 Issue 1 5...
Page 2: ......
Page 7: ...Document LT0400 4100ES S1 Programming Guide Introduction 1 1 1 Introduction...
Page 10: ...4100ES S1 Programming Guide Document LT0400 Introduction 1 4 THIS PAGE IS INTENTIONALLY BLANK...
Page 11: ...Document LT0400 4100ES S1 Programming Guide System Overview 2 1 2 System Overview...
Page 39: ...Document LT0400 4100ES S1 Programming Guide Adding Zone Displays 7 1 7 Adding Zone Displays...
Page 61: ...Document LT0400 4100ES S1 Programming Guide Custom Control 9 1 9 Custom Control...
Page 69: ...Document LT0400 4100ES S1 Programming Guide AS1668 Fan Controls 10 1 10 AS1668 Fan Controls...
Page 95: ...Document LT0400 4100ES S1 Programming Guide Appendices 12 1 12 Appendices...