4100ES-S1 Programming Guide
Document: LT0400
Appendices
12-2
12.1
Appendix A
– AS4428.1 Operation
A 4100ES-S1 that is required to comply with AS 4428.1 needs special functionality to be
implemented. This is done by a number of Custom Control equations.
Program 3 contains the system functions to provide brigade relay operation, common front
panel controls, battery testing and AVF. Program 4 contains the functions to operate the
zone alarm and fault LEDs and to use the Isolate pushbutton to isolate/de-isolate the zone
or general alarm/fault tests.
These programs should not be changed, except for removing unneeded zone equations in
Program 4, or adding zone equations when more zones are added.
Details of these programs are contained in the following sections.
AS4428.1 does not require the FireFighter Interface if individual zone level alarm and isolate
indicators are provided, which is why the 4100ES-S1 comes with 4100-1288 LED and
Switch modules. The LCD provides device level fault information and supplementary device
information for alarms and isolations.
Summary of Contents for 4100ES-S1
Page 1: ...4100ES S1 Fire Indicator Panel Programming Guide Australian Programming Guide LT0400 Issue 1 5...
Page 2: ......
Page 7: ...Document LT0400 4100ES S1 Programming Guide Introduction 1 1 1 Introduction...
Page 10: ...4100ES S1 Programming Guide Document LT0400 Introduction 1 4 THIS PAGE IS INTENTIONALLY BLANK...
Page 11: ...Document LT0400 4100ES S1 Programming Guide System Overview 2 1 2 System Overview...
Page 39: ...Document LT0400 4100ES S1 Programming Guide Adding Zone Displays 7 1 7 Adding Zone Displays...
Page 61: ...Document LT0400 4100ES S1 Programming Guide Custom Control 9 1 9 Custom Control...
Page 69: ...Document LT0400 4100ES S1 Programming Guide AS1668 Fan Controls 10 1 10 AS1668 Fan Controls...
Page 95: ...Document LT0400 4100ES S1 Programming Guide Appendices 12 1 12 Appendices...