4100ES-S1 Programming Guide
Document: LT0400
Adding Addressable Devices
5-4
Enter Custom Label into the Custom Label
box.
The Custom Label is limited to 40 characters.
It is recommended that the first characters be
the point address, followed by the description
of the point location and then lastly the zone
number, as the Event log does not record the
address or zone of the device.
e.g., M1-188 FOYER RECEPTION DESK
ZN01
To continue entering new devices click the
APPLY or NEXT buttons.
5.2
Assigning Devices to Zones
Once addressable devices have been entered into the configuration (refer Section 5.1) they can then
be assigned to Zones on the 4100ES-S1. This is done by adding the device to preset Lists as follows:
Select the
LIST
tab