Document: LT0400
4100ES-S1 Programming Guide
Adding Expansion Modules
8-7
Click the
Point Editing
tab and record the
points’ names. These names are used to
control the outputs within user defined
Custom Control equations as in the
following example for SIG9.
[INPUTS]
STATUS
ON
L257
| LIST | DPSEUDO | GENERAL FIRE
TRIP LIST (ACF ISOLATABLE)
[END INPUTS]
[OUTPUTS]
TRACK
ON
PRI
=
9
,
9
SIG9
| SIGB | SSIGNAL | SIGNAL CARD 5
CIRCUIT SIG9
[END OUTPUTS]
Refer to Chapter 9 for information on
writing Custom Control equations.