Document: LT0400
4100ES-S1 Programming Guide
Adding Zone Displays
7-3
Click on the “
+
” sign beside
the
DISPLAY CARDS
option
on the
Available Hardware
window.
Drag and drop the
4100-
1282
– 8 Pushbuttons/16
Red-Yellow LEDs
Icon over
the Bay 2 icon.
An 8
Pushbuttons/16 red-
Yellow LEDs
module will be
added to the configuration.
Repeat adding more
8
Pushbuttons/16 Red-
Yellow LEDs
modules as
required (up to 8 in total).
Notice that if more than 4 modules are configured then the 5
th
and higher will appear with a
‘[??]’
sign as follows:
This means that the configuration
requires an additional
4100-1288/1289
– F4 64 LED / 64
SW Controller
to be added.
Summary of Contents for 4100ES-S1
Page 1: ...4100ES S1 Fire Indicator Panel Programming Guide Australian Programming Guide LT0400 Issue 1 5...
Page 2: ......
Page 7: ...Document LT0400 4100ES S1 Programming Guide Introduction 1 1 1 Introduction...
Page 10: ...4100ES S1 Programming Guide Document LT0400 Introduction 1 4 THIS PAGE IS INTENTIONALLY BLANK...
Page 11: ...Document LT0400 4100ES S1 Programming Guide System Overview 2 1 2 System Overview...
Page 39: ...Document LT0400 4100ES S1 Programming Guide Adding Zone Displays 7 1 7 Adding Zone Displays...
Page 61: ...Document LT0400 4100ES S1 Programming Guide Custom Control 9 1 9 Custom Control...
Page 69: ...Document LT0400 4100ES S1 Programming Guide AS1668 Fan Controls 10 1 10 AS1668 Fan Controls...
Page 95: ...Document LT0400 4100ES S1 Programming Guide Appendices 12 1 12 Appendices...