4100ES-S1 Programming Guide
Document: LT0400
Adding Expansion Modules
8-6
8.3
Adding 4100-4321 6 Supervised Signal Card
The 4100-4321K 6 Supervised Relay module provides 6 supervised output control (signal)
circuits. The 6 circuits have two power inputs: one power input for every three signal circuits.
Each of the signal circuits is supervised for ground faults, opens and line-to-line shorts.
The card is added as follows:
Select the
HARDWARE
Tab.
Click on the “
+
” sign beside
Unit 0
.
Click on the “
+
” sign beside
Box
1
.
Cli
ck on the “
+
” sign beside
Bay
2
.
Click on the “
+
” sign beside the
SIGNAL
option on the
Available Hardware
window.
Drag and drop the
4100-4321- 3
Input Class B Sig
Icon over to
the
Bay 2
icon.
The card will be added to the panel configuration.
Double click on the card and in the
Card
Properties
tab adjust its address to be
greater than 4, then in the ‘
Card Custom
Label:
’ text box, enter a descriptive label.
Summary of Contents for 4100ES-S1
Page 1: ...4100ES S1 Fire Indicator Panel Programming Guide Australian Programming Guide LT0400 Issue 1 5...
Page 2: ......
Page 7: ...Document LT0400 4100ES S1 Programming Guide Introduction 1 1 1 Introduction...
Page 10: ...4100ES S1 Programming Guide Document LT0400 Introduction 1 4 THIS PAGE IS INTENTIONALLY BLANK...
Page 11: ...Document LT0400 4100ES S1 Programming Guide System Overview 2 1 2 System Overview...
Page 39: ...Document LT0400 4100ES S1 Programming Guide Adding Zone Displays 7 1 7 Adding Zone Displays...
Page 61: ...Document LT0400 4100ES S1 Programming Guide Custom Control 9 1 9 Custom Control...
Page 69: ...Document LT0400 4100ES S1 Programming Guide AS1668 Fan Controls 10 1 10 AS1668 Fan Controls...
Page 95: ...Document LT0400 4100ES S1 Programming Guide Appendices 12 1 12 Appendices...