4100ES-S1 Programming Guide
Document: LT0400
Appendices
12-16
12.4
Appendix D - Custom Control for Alarm Zone Facilities
A 4100-1282 8 Pushbutton/8 red LED/8 amber LED module is fitted for each 8 zones to
display the alarm and isolate states of the zones (lists) and allow the zone to be isolated,
alarm tested or fault tested.
This diagram shows the point numbers used for the push buttons and LEDs, where n = zone
number. A number of pseudo digital points are used for each zone to store and control the
operation.
3-65 Zone 1 Multifunction Button (P901)
x-x Zone n Multifunction Button (P900+n)
3-1 Zone 1 Alarm LED
3-2 Zone 1 Isolate LED (P601)
x-x Zone n Alarm LED
x-x Zone n Isolate LED (P600+n)
12.4.1
Digital Points used
Zone 1
P601
– Zone 1 is Isolated
P701
– Zone 1 Isolate Toggle
P801
– Zone 1 is in Alarm
P901
– Zone 1 Multifunction pushbutton
P1001
– Zone 1 is in Alarm Test
P1101
– Zone 1 is in Fault Test
Zone n
P600+n
– Zone n is Isolated
P700+n
– Zone n Isolate Toggle
P800+n
– Zone n is in Alarm
P900+n
– Zone n Multifunction pushbutton
P1000+n
– Zone n is in Alarm Test
P1100+n
– Zone n is in Fault Test
Summary of Contents for 4100ES-S1
Page 1: ...4100ES S1 Fire Indicator Panel Programming Guide Australian Programming Guide LT0400 Issue 1 5...
Page 2: ......
Page 7: ...Document LT0400 4100ES S1 Programming Guide Introduction 1 1 1 Introduction...
Page 10: ...4100ES S1 Programming Guide Document LT0400 Introduction 1 4 THIS PAGE IS INTENTIONALLY BLANK...
Page 11: ...Document LT0400 4100ES S1 Programming Guide System Overview 2 1 2 System Overview...
Page 39: ...Document LT0400 4100ES S1 Programming Guide Adding Zone Displays 7 1 7 Adding Zone Displays...
Page 61: ...Document LT0400 4100ES S1 Programming Guide Custom Control 9 1 9 Custom Control...
Page 69: ...Document LT0400 4100ES S1 Programming Guide AS1668 Fan Controls 10 1 10 AS1668 Fan Controls...
Page 95: ...Document LT0400 4100ES S1 Programming Guide Appendices 12 1 12 Appendices...