Document: LT0400
4100ES-S1 Programming Guide
Adding Expansion Modules
8-11
8.7
Adding 4100-0302/1290 24 Point Graphic Interface
The 4100-0302 24 Point Graphic Interface provides 24 points that can be configured as
inputs or outputs, with no restrictions on the
point’s allocation as input or output.
To add the 4100--0302 24 Point Graphic Interface to the panel:
Select the
HARDWARE
Tab.
Expand the
Unit 0
, ‘Box 1’ and
‘Bay 2’.
Click on the “
+
” sign beside the
LEGACY ANNUNCIATOR CARDS
option on the
Available Hardware
window.
Drag and drop the
4100-0302/1290
24 Point Graphic Interface
Icon
over to the
Bay 2
icon.
The card will be added to the panel
configuration.
Double click on the card and in the
Properties
Tab, select the card’s address
and enter in the
Card Custom Label:
text
box, a descriptive label.
Click the
Point Editing
tab and add/edit
the points’ device types, point types and
Custom Labels. Record the point
addresses, as they are used within user
defined Custom Control equations.
Summary of Contents for 4100ES-S1
Page 1: ...4100ES S1 Fire Indicator Panel Programming Guide Australian Programming Guide LT0400 Issue 1 5...
Page 2: ......
Page 7: ...Document LT0400 4100ES S1 Programming Guide Introduction 1 1 1 Introduction...
Page 10: ...4100ES S1 Programming Guide Document LT0400 Introduction 1 4 THIS PAGE IS INTENTIONALLY BLANK...
Page 11: ...Document LT0400 4100ES S1 Programming Guide System Overview 2 1 2 System Overview...
Page 39: ...Document LT0400 4100ES S1 Programming Guide Adding Zone Displays 7 1 7 Adding Zone Displays...
Page 61: ...Document LT0400 4100ES S1 Programming Guide Custom Control 9 1 9 Custom Control...
Page 69: ...Document LT0400 4100ES S1 Programming Guide AS1668 Fan Controls 10 1 10 AS1668 Fan Controls...
Page 95: ...Document LT0400 4100ES S1 Programming Guide Appendices 12 1 12 Appendices...