4100ES-S1 Programming Guide
Document: LT0400
Adding Expansion Modules
8-8
8.4
Adding 4100-5004 8 Point Monitor Card
The 4100-5004 8 Point Monitor Card provides eight conventional detector or contact closure
inputs. There are no restrictions on point types.
To add the 4100-5004 8 Point Monitor Card to the panel:
Select the
HARDWARE
Tab
Expand the
Unit 0
, ‘Box 1’ and
‘Bay 2’.
Click on the “
+
” sign beside the
MONITOR
option on the
Available
Hardware
window.
Drag and drop the
4100-5004/5005
8 Point Class B Sec Monitor
Icon
over to the
Bay 2
icon.
The card will be added to the panel
configuration.
Double click on the card and in the
Properties
Tab, select the card’s address
and enter in the
Card Custom Label:
text
box, a descriptive label.
Click the
Point Editing
tab and add/edit
the points’ point types and names. Record
the points’ names as they may be used
within user defined Custom Control
equations as in the following example for
ZN1 and SIG9.
When ZN1 (this point) is in ALARM,
operate SIG9.
[INPUTS]
STATUS
FIRE
ZN1
| SMONB | FIRE | MONITOR CARD 7
ZONE ZN1
[END INPUTS]
[OUTPUTS]
TRACK
ON
PRI
=
9
,
9
SIG9
| SIGB | SSIGNAL | SIGNAL CARD 5
CIRCUIT SIG9
[END OUTPUTS]
Summary of Contents for 4100ES-S1
Page 1: ...4100ES S1 Fire Indicator Panel Programming Guide Australian Programming Guide LT0400 Issue 1 5...
Page 2: ......
Page 7: ...Document LT0400 4100ES S1 Programming Guide Introduction 1 1 1 Introduction...
Page 10: ...4100ES S1 Programming Guide Document LT0400 Introduction 1 4 THIS PAGE IS INTENTIONALLY BLANK...
Page 11: ...Document LT0400 4100ES S1 Programming Guide System Overview 2 1 2 System Overview...
Page 39: ...Document LT0400 4100ES S1 Programming Guide Adding Zone Displays 7 1 7 Adding Zone Displays...
Page 61: ...Document LT0400 4100ES S1 Programming Guide Custom Control 9 1 9 Custom Control...
Page 69: ...Document LT0400 4100ES S1 Programming Guide AS1668 Fan Controls 10 1 10 AS1668 Fan Controls...
Page 95: ...Document LT0400 4100ES S1 Programming Guide Appendices 12 1 12 Appendices...