Symptom
Cause
Solution
Defective cylinder
Replace cylinder
A different status is
displayed in LSM to
the actual status
LSM has not been
synchronised with the
cylinders
See 'Forward events'
in this section for
description
Network connection
unstable
Check whether
network is available,
e.g. read cylinder over
the network. Check
signal strength: at
least 70 dB.
Examine surroundings
for sources of
interferences, such as
fluorescent tubes, dim
switches, generators,
mains adapters
Forward events
If the door statuses are not displayed in LSM, check the network
configuration.
First, determine the locking device's network detection
ü
The 'Network' column is shown in the locking plan. The 'W' is
visible in the locking plan
1.
Position the mouse cursor on the 'W' in the locking plan > The
WaveNet node number is displayed, e.g. WNNode_0026
2.
Note down the identifier for later use
Activate input events
The input events must be activated, so that events can be transmitted
from the cylinder to the LockNode
1.
Open the menu item 'Network' > 'Collective tasks' > 'WaveNet
nodes'
2.
Highlight the node which features the number that you wrote
down earlier
3.
Click on [Activate input events]
ð
The input events are activated
1.
Open WaveNet administration > 'Network' > 'Administer
WaveNet'
2.
Select the network segment with the required WaveNet node
3.
Highlight the door 'Nodes/addresses'
4.
Click on [Properties]
5.
Activate the check mark for 'Activate forwarding of events' in the
'Configuration' section