Symptom
Cause
Solution
Fastening screw too
short.
No contact between
the sensor in the
fastening screw and
the cylinder
Remeasure backset
Order fastening screw
according to backset
size
DM Cylinder
configured incorrectly
Check DM Cylinder
configuration.
Is there a check mark
against 'Door open' in
the access list?
Is transmission via
network configured?
Is sampling interval
configured for
fastening screw?
Flipflop mode or time
switchover
configured?
> The bolt status
cannot be checked
Input events via
WaveNet not
configured
Configure input events
by selecting Network/
Group tasks/WaveNet
node / Activate input
events
Event forwarding not
activated
Check whether status
has been read Set
check mark against
Event forwarding
Also select WaveNet
node properties at
Network / Administer
WaveNet
Defective cylinder
Replace cylinder
Manual
Door Monitoring Cylinder