69/238
Building Technologies
Modular Heating Controller RMH760B
CE1P3133en
HVAC Products
6 Boiler temperature control
05.02.2007
Depending on the type of hydraulic system used, this may not be required (e.g. bypass
pump).
DC 0…10 V output for a DC 0…10 V mixing valve actuator.
For more detailed information, refer to subsection 6.6.11 “Maximum limitation of the
boiler temperature”.
6.3
Boiler operating modes and boiler setpoints
Main menu > Boiler > Boiler operating mode
Operating line
Range
Factory setting
Preselection
Auto /
Release DHW / Off
Auto
Setp preselection manual
---- / 8…140 °C
----
State On
/
Off
Cause
Commissioning /
Frost protection for consumer /
Overtemp protection/overrun /
Frost protection for boiler /
Operating mode selector /
Prot boil startup Boiler /
Release delay burner /
Outside temperature lock /
Minimum limitation boiler /
Test mode /
Flue gas measuring mode /
Request /
No request
The user can switch the boiler off via operation.
In operating mode “Release DHW“, only heat requests from DHW (digital input or via
Konnex bus) will be taken into consideration.
If “Off” is preselected, the internal frost protection function remains active. Heat re-
quests from an external consumer resulting from frost protection will also be consid-
ered.
This setting can be used to preselect a minimum request for the boiler controller, which
means that a maximum selection based on the consumers' requests will be maintained.
The boiler’s state is indicated (On / Off).
It is indicated why the current state is active.
The boiler temperature setpoint will be generated based on the temperature requests
received from the consumers plus the setpoint increase.
The boiler temperature setpoint and the actual boiler temperature can be called up on
the info level.
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Boiler > Operation settings
Operating line
Range
Factory setting
Setpoint increase
0…50 K
0 K
Maintained boiler return
temperature, continu-
ously
Plant operation selector
Preselection
Manual preselection
of setpoint
State
Cause
Boiler temperature set-
points