206/238
Building Technologies
Modular Heating Controller RMH760B
CE1P3133en
HVAC Products
14 Communication
05.02.2007
With master / slave operation, this setting is used to make the zone assignment. In that
case, the slave devices are given the same holidays/special day zone as the master.
It is possible to define several zones with one master per zone.
RM..
RM..
31
31
Z
10
Holiday/special day
Device 2
Calendar operation: Master
Device 1
Calendar operation: Slave
Calendar zone:
1
Holiday/Special day
Calendar zone:
1
14.3 Room
data
Every heating circuit belongs to a geographical zone. This zone symbolizes the room to
be controlled. Within the zone, all room-related data will be exchanged:
•
Room operating mode
•
Room temperature
•
Setpoints
14.3.1 Communication
variants
The requirements (operation, function) placed on the generation of the room operating
mode differ significantly, depending on the type of building and its usage. The commu-
nication variants described below allow the determination of the room operating mode
to be adapted to the requirements.
Basic variant 1 assumes that a heating circuit has its own individual room operating
mode, independent of other plant (heating circuits, ventilation). This means that the
exchange of data is restricted to the heating circuit and the rooms in the relevant geo-
graphical zone.
If there is a room unit in that zone, the heating circuit will automatically receive its room
temperature and setpoint readjustments. In addition, data are exchanged to determine
the room operating mode.
QAW740
RM..
31
31
Z
08
Geographical zone: 5
Room temperature
Geographical zone: 5
Room unit
Heating circuit 1
Room temperature
Holidays/special day zone
Individual room usage
(variant 1)