50/238
Building Technologies
Modular Heating Controller RMH760B
CE1P3133en
HVAC Products
5 General functions, fundamentals
05.02.2007
Main menu > Commissioning > Extra configuration > Heating circuit 1
(
or
2
or
3
)
> Inputs
Main menu > Commissioning > Extra configuration > DHW > Inputs
Operating line
Range
Factory setting
Special day input
--- / RMH760… etc.*
---
Holiday input
--- / RMH760… etc.*
---
* These inputs are only active if holidays/special day operation has been set to “Autonomous“ or “Master”.
The digital input enables the plant to be switched to the special day program set in the
7-day program. If the configured input is activated, the special day program will become
active. This state is maintained until the input becomes inactive. Then, the normal 7-
day program will be resumed.
The digital input enables the plant to be switched to “Holidays” mode.
When the configured input is activated, the plant switches to “Holidays” mode. This
state is maintained until the input becomes inactive. Then, the normal 7-day program
will be resumed.
If, at the same time, a special day or a holiday period is activated via the control
switches and an entry in the calendar, the following priority will apply:
1. Control switch ”Special day”
2. Control switch “Holidays”
3. “Special day” entry in the calendar
4. “Holidays” entry in the calendar
If other controllers are also configured as slaves in the same holidays / special day
zone, the digital inputs will act on these controllers also.
5.2.6 Fault
handling
Only one master may be set per holidays / special day zone. If there is more than one
master in a zone, fault status message
>1 hol/sp day prgm HC 1
(or
…HC 2
or
…HC 3
or
…DHW
) will be delivered.
The fault is identified by the holidays / special day master (A) when it receives a holi-
days / special day signal from some other master (B) in its zone. Master ”A” will then
display a fault status message and forward it, but no more holidays / special day signal,
in order to prevent the slaves from switching back and forth.
If the controller expects a holidays / special day signal from the bus, but same signal is
not transmitted, fault status message
Hol/sp day prgm failure HC 1
(or
…HC 2
or
…HC 3
or
…DHW
) will be delivered.
The operating modes of the 7-day program are used, without giving consideration to
the holidays / special day entries.
Number Text
Effect
5201
Hol/sp day prgm failure HC 1 Nonurgent message; must not be ac-
knowledged
5211
Hol/sp day prgm failure HC 2 Nonurgent message; must not be ac-
knowledged
5221
Hol/sp day prgm failure HC 3 Nonurgent message; must not be ac-
knowledged
5231
Hol/sp day prgm failure
DHW
Nonurgent message; must not be ac-
knowledged
5202
>1 hol/sp day prgm HC 1
Nonurgent message; must be acknowl-
edged
Setting
Special day
Holidays
Priority
Note
Fault status messages