6 Boiler temperature control
05.02.2007
6.7
Flue gas temperature supervision
Flue gas temperature supervision offers:
•
Display of the current flue gas temperature
•
Display of the maximum flue gas temperature acquired after a selected point in time
•
Supervision of the flue gas temperature limit including alarm should the limit value be
exceeded
An appropriate sensor must always be configured, independent of usage.
Main menu > Commissioning > Extra configuration > Boiler > Inputs
Operating line
Adjustable values / display / remarks
Flue gas temperature sensor
Assign input
In contrast to the other temperature inputs, where the default configuration is a Ni1000
sensor, sensor type Pt1000 is used here. The type of sensor can be adapted under
Settings > Inputs
at the configured terminal.
Through configuration of the sensor, the following functions are made possible:
This function is active as soon as a flue gas temperature sensor is configured.
Main menu > Boiler > Inputs/setpoints
Operating line
Adjustable values / display / remarks
Flue gas temperature maximum
It is always the maximum flue gas temperature that is saved and displayed. The dis-
played value can be adjusted like a setting value (e.g. to 0 °C), whereupon the slave
pointer will start at zero again.
The maximum value is filtered to suppress faults. This means that the maximum flue
gas temperature rises at a maximum rate of 1 K/s.
If a flue gas temperature limit value is parameterized, a fault status message will be
delivered should the limit value be exceeded.
Main menu > Commissioning > Settings > …
or
Main menu
>
Settings > Boiler > Fault settings > Flue temp supervision
Operating line
Range
Factory setting
Flue gas temperature limit value
---- / 0…400 °C
---- °C
When the actual flue gas temperature lies 5 K below the maximum value, the fault
status message can be reset by making an acknowledgement. When resetting, the
slave pointer value is also reset to the current value.
Main menu > Commissioning > Settings > …
or
Main menu
>
Settings > Boiler > Fault settings > Flue temp supervision
Operating line
Range
Factory setting
Impact of fault
No stop / Stop
No stop
Fault priority
Urgent / Nonurgent
Nonurgent
When a flue gas limit temperature is monitored, it can also be determined whether
crossing of the limit value shall cause the boiler to shut down (No stop / Stop).
Main menu > Boiler > Inputs/setpoints
Operating line
Adjustable values / display / remarks
Flue gas temperature
Flue gas temperature maximum
The current flue gas temperature and the maximum flue gas temperature are available
as diagnostic values.
Slave pointer function
Supervision of maximum
value
Supervision of maximum
value and boiler stop
Diagnostic values