119/238
Building Technologies
Modular Heating Controller RMH760B
CE1P3133en
HVAC Products
9 Heating circuit control
05.02.2007
10
4
Off, Auto
On, Off
On, Off
9
On, Off
Cmf, Pcf, Eco, Prt
11
1
On, Off
3
5
8
7
2
On, Off
12
3133Z
14
On, Off
6
Auto, Cmf,
Pcf, Eco, Prt
Cmf, Pcf, Eco, Prt
Timer button
(pushbutton at
digital Input)
Settings calendar
Plant operating mode selector
Special day, holidays
Resulting operating mode
Cmf, Pcf, Eco, Prt
Holiday
contact
Special day
contact
Pump, mixing valve
Interventions
via digital inputs
Operating on the controller,
or room unit, or via bus
Wiring test
Calendar
Switching program
Resulting operating mode
Time program Cmf, Pcf, Eco, Prt
Settings 24-hour program,
holiday/special day program
Room
operating
contact
Room operating mode selector
on RMH760B controller
On, Off
Timer button
Presence button
User
requisition
From user requisition room
(RMU7... controller)
Heating circuit
control (part plant)
Resulting control command
pump, mixing valve
Timer button or mode button
on QAW740 room unit
T
im
e sw
itch
Priority Name
Explanation
1
Wiring test
In the wiring test (highest priority), the plant compo-
nents can be directly controlled, independent of all
other settings
The controller-internal safety functions will
be overridden!
2
External master
The plant operation selector has the second highest
priority and can only be overridden by the control-
ler’s frost protection function
Room optg mode
contact
If the heating circuit operates in a room control
combination as a slave, the operating mode is
preselected by the external master (heating circuit
or ventilation).
In that case, interventions of priority
f
through
can only be made on the master
Room operating mode
selector
Using the room operating contact, a fixed operating
mode can be preselected. This operating mode
overrides room operation selector
g
on the control-
ler
External master
The room operation selector can be used to switch
from operating mode
to a continuous oper-
ating mode with the respective setpoint.
In operating mode
, the setpoint is deter-
mined by the time switch or the presence button
and the timer