The heating circuit can be configured to any type of module. If the RMZ782B is re-
placed by some other module, all settings using type reference RMZ782B… via “Extra
configuration“ must be reconfigured.
Function blocks can always be activated via “Extra configuration“, independent of the
type of plant. A function block is activated by assigning an output to a terminal. Here,
the heating circuit can be configured to any terminals that are free. If all outputs of the
heating circuit are set invalid, the heating circuit will be deactivated.
For weather-compensated heating circuit control, the outside temperature is required. It
can be configured as follows:
•
For heating circuit 1, on the following menu:
Main menu > Commissioning > Extra configuration > Miscellaneous > Inputs > Outside sensor
•
For the 2 other heating circuits, on the following menu:
Main menu > Commissioning > Extra configuration > Heating circuit 2
(or
3
)
> Inputs > Outside
sensor
The outside temperature can also be transmitted via the Konnex bus.
In addition, a solar intensity sensor and wind speed sensor for common usage by all
heating circuits can be configured on the following menu:
Main menu > Commissioning > Extra configuration > Miscellaneous > Inputs
The impact on the
individual heating circuits can be parameterized.
For more detailed information, refer to section 14.6 “Weather data”.
Main menu > Commissioning > Extra configuration > Heating circuit 1
(or
2
or
3
)
> Inputs
Operating line
Adjustable values / display / remarks
Outside sensor*
Flow sensor
Room sensor
Return sensor
Return temperature limitation
Room setpoint adjuster abs
External room temperature setpoint adjuster
with absolute room temperature setpoints
Room setpoint adjuster rel
External room temperature setpoint adjuster
with room temperature setpoint readjust-
ment of ±3 K
[Heating circuit pump] overload
Fault input heating circuit pump
[Heat circuit pump B] overload
Pump B in the case of twin pumps
Flow signal pump
Flow supervision heating circuit pump(s)
Room operating mode
External preselection
Timer function
Comfort extension
Special day input
Holiday input
* Outside sensor:
Only heating circuits 2 and 3 have their own outside temperature. Heating circuit 1 shares the outside tem-
perature with other function blocks in the controller. The outside sensor is to be configured under
… > Miscel-
laneous > Inputs
.
Main menu > Commissioning > Extra configuration > Heating circuit 1
(or
2
or
3
)
> Outputs
Operating line
Adjustable values / display / remarks
Outside temperature relay*
Mixing valve 3-pos
Mixing valve modulating
Heating circuit pump
Heating circuit pump B
Extra configuration
Outside sensor
Solar intensity and wind
speed sensor
Inputs
Outputs