125/238
Building Technologies
Modular Heating Controller RMH760B
CE1P3133en
HVAC Products
9 Heating circuit control
05.02.2007
0
5
10
15
20
25
TOstrDmp
TOeff
t
31
31D
23
TO
TO
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Heating circuit 1
(or
2
or
3
)
> Space heating
Operating line
Range
Factory setting
Building time constant
0…200 h
20 h
Main menu > Heating circuit 1
(or
2
or
3
)
> Heating curve
Operating line
Range
Factory setting
Proportion of windows
0…100 %
50 %
9.5.2
Heating curve
The heating curve is defined by 2 curvepoints:
1
: At the design temperature
•
By the outside temperature TODef
A
•
By the flow temperature SetPTFlDef
B
2
: At the theoretical heating limit
•
By the outside temperature TOHi
C
•
By the flow temperature SetPTFlHi
D
SetPTFlDe
SetPTFlHi
SetPTRN
TFl
TOeff
TODe
sHC
TOHi
B
D
A
C
1
2
31
31
D
24
The nonlinear heat transmission is considered by the radiator exponent nH. The follow-
ing table gives an overview of the different types of heating systems normally used:
Heat transmission via…
Radiator exponent nH
Underfloor heating system
1.05…1.1
Flat radiators
1.26…1.33
Radiators to DIN 4703
1.3
Convectors
1.25…1.45
Settings
Heating curve
Curvepoints
Radiator exponent