7 Heat demand and heat requests
05.02.2007
To ensure that minimum opening travel of the valve will not generate a demand for
heat, a switch-on or switch-off threshold can be defined. The factory settings are as
follows:
•
A demand for heat will be calculated only when the valve positions are >10 %
•
When the valve positions of all consumers are <5 %, the demand for heat will be
suppressed again
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Primary controller > Demand control
Main menu > Settings > Main controller > Demand control
Main menu > Settings > Boiler > Demand control
Operating line
Range
Factory setting
[Curvepoint 1] outside temp
–50…50 °C
–10 °C
[Curvepoint 1] flow temp
0…140 °C
70 °C
[Curvepoint 2] outside temp
–50…50 °C
20 °C
[Curvepoint 2] flow temp
0…140 °C
70 °C
Flow temp correction max
0…100 K
10 K
Control mode
Slow / Medium / Fast
Medium
Request evaluation
Maximum / Average
Maximum
Limit value request on
Off value…100 %
10 %
Limit value request off
0…On value %
5 %
31
31
D20
1
2
Outside
temperature
Flow temperature
(Curvepoint 1):
Outside temp.
Max. flow temp.
readjustment
(Curvepoint 1):
Flow temp.
(Curvepoint 2):
Flow temp.
(Curvepoint 2):
Outside temp.
Adaptation of the flow temperature can be set as follows:
•
The rate of change of flow temperature readjustment can be set under
> Demand
control > Control action
•
The kind of evaluation of the consumers’ valve positions can be selected under
> Demand control > Request evaluation
−
When using the
Maximum
setting, the flow temperature will be readjusted in a
way that the valve position of the consumer with the greatest heat demand is 90
%
−
When using the
Average
setting, the flow temperature will be readjusted in a way
that the valve positions of the 4 largest consumers will be 90 % on average
This setting does not ensure that the heat demand of all consumers can be satis-
fied. It makes certain, however, that an individual consumer cannot force the flow
temperature to high levels (e.g. because a window was left open).
The heating curve settings of the heat demand transformers also apply to the heat
demand contact of the heating curve (operating line
Heating curve request 2-pos
).
Adaptation of the flow
temperature
Note