FEC920: USER GUIDE
Page 40
A
September 18
An alternative to the click-drag technique is to right click on the required output (five in the example below), and
select ‘Edit Wire...’ from the context menu that appears. A browse window pops up, allowing the user to navigate
to the required parameter. This technique can be used both on previously empty inputs or outputs and on those
previously filled.
Figure 30 Context menu details
EXPLICIT DATA
As shown in Figure 31, when configured as a server, there is only one explicit application object, and that has
the class ID= A2 (162 decimal). The instance ID is the Modbus address of the parameter and the Attribute is
always = 1. Explicit service codes hex10 (decimal 16) and 0E (14) are both supported, for writing and reading
single attributes respectively.
Figure 31 Explicit data specification
When configured as a client, two separate connections are available allowing the user to produce two
independent explicit read or write messages to different server devices.
Figure 32, shows an example of how to configure an explicit message request. The instance ID and the data
type are taken from the server manufacturer’s data. In this example a read request is configured to determine
the Group recording status of a
FEC920
server, and it can be seen from the table in Section 7.3 on page 132
that the decimal Modbus address for this parameter is 4150 and the data type is int16. It is this address which
is used as the instance ID.
Once all the information has been entered, the read is requested by setting ‘Send’ to ‘Yes’. The Data field
changes to ‘3’ for this example and from the table in Section 7.3 on page 132 it can be seen that the recording
status is ‘Recording enabled’.
Note:
The
FEC920
supports only 16 bit data types for reading and writing of explicit messages.
Service code
Class ID
Instance ID
Attribute
Hex
Dec
Hex
Dec
Decimal
0010
16
A2
162
1-65535
1
000E
14
A2
162
1-65535
1
A5E45696052A Rev-AA