Adjusting the voltage monitoring relay -A11 (only necessary when replacing)
①
Start-up bridging duration
②
Overvoltage trip threshold
③
Undervoltage trip threshold
④
Tripping delay time duration
⑤
Operating mode
Figure 3-14 Voltage monitoring relay -A11
Follow the procedure below to adjust the threshold of the overvoltage trip with a voltmeter:
1. Ensure that only the auxiliary voltage is connected (the circuit-breaker is open).
2. Set the potentiometer "MAX" to 100%.
3. Measure the voltage at the measuring input "U1" of the voltage monitoring relay -A11. Set
the output voltage of the associated SITOP supply -G11 to the threshold value
25.8 V ± 0.1 V.
4. Slowly reduce the threshold value "MAX" of the voltage monitoring relay -A11 until it trips.
Leave the potentiometer in this setting. The red "MAX" LED " is illuminated, the yellow
"REL" LED is off. After the tripping operation, the measured value on measuring input "U1"
increases by approximately 0.4 V, because the load is disconnected due to the shutdown
and thus the voltage drop via the miniature circuit-breaker is also omitted.
5. Reduce the SITOP output voltage to approximately 24 V.
6. Switch off the miniature circuit-breaker F11 and then switch it on again.
7. To verify the trip level, slowly increase the SITOP output voltage until the tripping operation
of the voltage monitoring relay -A11. In this process, measure the trip value on the
measuring input "U1". This value must be between the limit values of 25.2 V - 26.4 V.
Description
3.6 Description of options
SINAMICS SM150 6SL3845-7NN46-7AA0
66
Operating Instructions 04/2017
Summary of Contents for SINAMICS SM150
Page 2: ...20 04 2017 13 53 V27 00 ...
Page 14: ...Table of contents SINAMICS SM150 6SL3845 7NN46 7AA0 14 Operating Instructions 04 2017 ...
Page 122: ...Start up SINAMICS SM150 6SL3845 7NN46 7AA0 122 Operating Instructions 04 2017 ...
Page 190: ...Maintenance 9 7 Repairs SINAMICS SM150 6SL3845 7NN46 7AA0 190 Operating Instructions 04 2017 ...
Page 192: ...Spare parts SINAMICS SM150 6SL3845 7NN46 7AA0 192 Operating Instructions 04 2017 ...
Page 196: ...Service Support SINAMICS SM150 6SL3845 7NN46 7AA0 196 Operating Instructions 04 2017 ...
Page 217: ......