Item
Activity
Available
/completed
Option K50
Sensor Module
for detecting the
actual motor
speed
If a function for detecting the actual speed value is provided to improve
speed accuracy, connect the motor rotary pulse encoder to the SMC30
( A... ).
Option L32
Voltage Sens‐
ing Module
If, for process-related reasons, the drive needs to be restarted after
power failures of > 100 ms, connect the synchronization voltage of the
line upstream of the medium-voltage circuit-breaker to the VSM 10. To
do so, install voltage converters at the medium-voltage level, which
supply 3-phase 100 VAC as the synchronization voltage. Connect the
voltage converters on the drive side to terminals.
Switch-on conditions with water-cooled drives
Before switching on the drive for the first time, you must reduce the conductivity of the de-
ionized water circuit to < 1 µS. After filling the re-cooling unit, switch it on for several hours
before switching on the drive. The conductivity reduction may also be necessary if the
drive has been out of service for an extended period (such as maintenance/revision times).
Required tools
To install the connections, you will require:
● Spanner or socket spanner (w/f 10)
● Spanner or socket spanner (w/f 13)
● Spanner or socket spanner (w/f 16/17)
● Spanner or socket spanner (w/f 18/19)
● Hexagon-socket spanner (size 8)
● Torque spanner, max. 50 Nm
● Screwdriver, size 2
● Screwdriver, Torx T20
● Screwdriver, Torx T30
Checklists and forms
C.2 Checklist for electrical installation
SINAMICS SM150 6SL3845-7NN46-7AA0
214
Operating Instructions 04/2017
Summary of Contents for SINAMICS SM150
Page 2: ...20 04 2017 13 53 V27 00 ...
Page 14: ...Table of contents SINAMICS SM150 6SL3845 7NN46 7AA0 14 Operating Instructions 04 2017 ...
Page 122: ...Start up SINAMICS SM150 6SL3845 7NN46 7AA0 122 Operating Instructions 04 2017 ...
Page 190: ...Maintenance 9 7 Repairs SINAMICS SM150 6SL3845 7NN46 7AA0 190 Operating Instructions 04 2017 ...
Page 192: ...Spare parts SINAMICS SM150 6SL3845 7NN46 7AA0 192 Operating Instructions 04 2017 ...
Page 196: ...Service Support SINAMICS SM150 6SL3845 7NN46 7AA0 196 Operating Instructions 04 2017 ...
Page 217: ......