9. Fasten the four eyebolts
⑫
on the phase module. Position the stacker so that you can
hang the eyelets on the fork.
Figure 9-21 Phase module (placed down)
10.Lift up the phase module and put it to one side.
11.Now lift the new phase module in the same manner from the transport packaging. Place
the phase module on the changing device.
Installing the module
1. Install the intact module in the reverse order of the previously described steps.
2. When tightening the screws, make sure that you use the appropriate torque (Page 170)
permissible for each screw type.
3. Tighten the joints between the water pipes by hand.
Performing final checks
1. Open the valves.
2. Make sure that the connections are tight.
3. Make sure that the flow is ensured once the re-cooling unit has been switched in.
Maintenance
9.7 Repairs
SINAMICS SM150 6SL3845-7NN46-7AA0
Operating Instructions 04/2017
179