3.6
Description of options
3.6.1
NAMUR terminal strip (option B00)
The NAMUR command source is a terminal strip that is equipped with isolation amplifiers and
relays and is located upstream of Terminal Modules TM31 and TM15.
Note
The inputs and outputs assigned to the terminals fulfill PELV (Protective extra-low voltage)
requirements.
The NAMUR terminal strip fulfills the requirements and guidelines of the standards association
for measurement and control technology in the chemical industry (NAMUR recommendation
NE37).
On the NAMUR terminal strip, certain device functions are assigned to fixed terminals. The
fixed assignment between drive signals and the NAMUR terminals represents your
standardized control logic in the converter and fulfills the requirements for protective separation.
To monitor the temperature of explosion-protected motors, options for PTC tripping devices
with PTB approval and PT100 for use in hazardous areas are available.
See also
Terminal assignment of the NAMUR terminal strip (option B00) (Page 202)
3.6.2
Isolation amplifiers for optional analog inputs (option E86)
This option provides two isolation amplifiers if an additional TM31 Terminal Module is provided
as an extension of the customer interface and the TM31 analog inputs are to be used with a
higher-level control level for communication purposes. Multifunction interface converters with
the following adjustment range are used:
● 0 V to 10 V
● 0 mA to 20 mA
● 4 mA to 20 mA
The range must be set on the isolating transformer.
Description
3.6 Description of options
SINAMICS SM150 6SL3845-7NN46-7AA0
52
Operating Instructions 04/2017
Summary of Contents for SINAMICS SM150
Page 2: ...20 04 2017 13 53 V27 00 ...
Page 14: ...Table of contents SINAMICS SM150 6SL3845 7NN46 7AA0 14 Operating Instructions 04 2017 ...
Page 122: ...Start up SINAMICS SM150 6SL3845 7NN46 7AA0 122 Operating Instructions 04 2017 ...
Page 190: ...Maintenance 9 7 Repairs SINAMICS SM150 6SL3845 7NN46 7AA0 190 Operating Instructions 04 2017 ...
Page 192: ...Spare parts SINAMICS SM150 6SL3845 7NN46 7AA0 192 Operating Instructions 04 2017 ...
Page 196: ...Service Support SINAMICS SM150 6SL3845 7NN46 7AA0 196 Operating Instructions 04 2017 ...
Page 217: ......