B.2.4
Interfaces of the Power Stack Adapter
B.2.4.1
Gating of the power semiconductors
Number Duplex fiber-optic
cable
Meaning:
Gating power semiconductors
Technical data
①
X11 to X14
Inverter phase u
Fiber-optic cable type: 2 mm
plastic optical fiber (POF)
Max. length of fiber-optic cable:
20 m
③
X31 to X34
Inverter phase v
⑤
X51 to X54
Inverter phase w
②
X15 / X16
Crowbar
④
X35 / X36
Braking chopper
B.2.4.2
Selecting Safe Torque Off
Interface
Terminal Designation
Technical data
X241
1
+24 V (internal)
Relay, coil data:
● Rated voltage: 24 V DC
● Operating range: 21.6 to 26.4 V DC
Relay, contact data:
● Single contact, positively driven
● Rated current: 8 A
● Rated voltage / max. switching voltage: 240/400
V AC
● Max. switching power 12 W (24 V, 500 mA)
2
Relay coil 1 (+)
3
NC contact
X242
1
M
2
Relay coil 2 (-)
3
NC contact
Note
The internal safety relay must be energized in order to operate the inverter (see Chapter
"Gating the power semiconductors"). If the option "Safe Torque Off (STO)" is not available,
this circuit function is achieved permanently by inserting jumpers between terminals 1 and 2
of the two connectors X241 and X242.
If the option "Safe Torque Off (STO)" is used, the safety relay is controlled by the two terminals
2 of connectors X241 and X242. The feedback information from the NC contact terminal 3 at
X241 and X242 is evaluated in a higher-level safety control to check the switching state.
Technical data and drawings
B.2 Terminal assignments
SINAMICS SM150 6SL3845-7NN46-7AA0
204
Operating Instructions 04/2017
Summary of Contents for SINAMICS SM150
Page 2: ...20 04 2017 13 53 V27 00 ...
Page 14: ...Table of contents SINAMICS SM150 6SL3845 7NN46 7AA0 14 Operating Instructions 04 2017 ...
Page 122: ...Start up SINAMICS SM150 6SL3845 7NN46 7AA0 122 Operating Instructions 04 2017 ...
Page 190: ...Maintenance 9 7 Repairs SINAMICS SM150 6SL3845 7NN46 7AA0 190 Operating Instructions 04 2017 ...
Page 192: ...Spare parts SINAMICS SM150 6SL3845 7NN46 7AA0 192 Operating Instructions 04 2017 ...
Page 196: ...Service Support SINAMICS SM150 6SL3845 7NN46 7AA0 196 Operating Instructions 04 2017 ...