![Siemens SINAMICS SM150 Operating And Installation Instructions Download Page 209](http://html.mh-extra.com/html/siemens/sinamics-sm150/sinamics-sm150_operating-and-installation-instructions_378231209.webp)
Checklists and forms
C
C.1
Mechanical installation: Checklist
Logbook
Use the following checklist to guide you through the mechanical installation procedure for the
cabinet unit. Read the safety information at the start of these operating instructions before you
start working on the device.
Note
If the option in question is part of the delivery, check this accordingly in the right-hand column.
Check the boxes once you have finished the installation procedure to confirm that the activities
are complete.
Item
Activity
Available / Completed
1
The environmental conditions must be permissible. For more information, see the "Tech‐
nical specifications" section.
If the drive and re-cooling unit are installed separately, the bottom level (switch-off level)
of the expansion tank must be located above the highest water level in the drive.
2
Connect the raw water circuit and the de-ionized water circuit. Remove any contamination
from the piping that may have occurred during shipment or storage.
3
Fill and vent the de-ionized water circuit according to the specifications. Ensure that no
air is trapped in the piping system.
4
Install the separately supplied components. Make the required mechanical and electrical
connections as well as the connection to the de-ionized water circuit.
5
The clearance around an open door (escape route) specified in the applicable accident
prevention guidelines must be observed.
6
For option M13/M78:
Select the required metric gland or PG gland appropriate for the cable cross-section.
Proivde the appropriate holes in the cover plates. When the cable is fed in from above,
ensure that enough room is available if the cable has to be bent because of the cable
feeder and cross-sections. To prevent lateral forces on the entries, insert the cable verti‐
cally.
SINAMICS SM150 6SL3845-7NN46-7AA0
Operating Instructions 04/2017
209
Summary of Contents for SINAMICS SM150
Page 2: ...20 04 2017 13 53 V27 00 ...
Page 14: ...Table of contents SINAMICS SM150 6SL3845 7NN46 7AA0 14 Operating Instructions 04 2017 ...
Page 122: ...Start up SINAMICS SM150 6SL3845 7NN46 7AA0 122 Operating Instructions 04 2017 ...
Page 190: ...Maintenance 9 7 Repairs SINAMICS SM150 6SL3845 7NN46 7AA0 190 Operating Instructions 04 2017 ...
Page 192: ...Spare parts SINAMICS SM150 6SL3845 7NN46 7AA0 192 Operating Instructions 04 2017 ...
Page 196: ...Service Support SINAMICS SM150 6SL3845 7NN46 7AA0 196 Operating Instructions 04 2017 ...
Page 217: ......