SICAM Q80 7KG8080
Power Quality Recorder SICAM Q80 7KG8080, System manual
E50417-H1076-C420-A2, Release 12.01.2015
Coils addresses 60 through 65: Commands for the measurement device
No
Register-
offset
Content
Format
Unit
Sample value
Value range
31
60
Stop
bool16
0
Set to 1
32
61
Close Datapath
bool16
0
Set to 1
33
62
Reset Extrema
U1..U4, I1..I4
bool16
0
Set to 1
34
63
Reset Extrema
U5..U8
bool16
0
Set to 1
35
64
Reset Extrema Power
bool16
0
Set to 1
36
65
Reset 4Q counter
bool16
0
Set to 1
Holding Register from address 80 on: Measured data
No
Register-
offset
Content
Format
Unit
Sample value
Value range
37
80
Digital IN
int16
-
5
20 DI Bit 1
21 DI Bit 2
22 DI Bit 3
23 DI Bit 4
38
81
Digital Out
int16
-
1
20 DO Bit 1
21 DO Bit 2
22 DO Bit 3
23 DO Bit 4
39
82
Digital Out
int16
-
1
0 = No measurement or not
activated
1 = measurement running - ok
3 = measurement off (error or
stop)
General states, event count
40
100
free memory
float32
Mbyte
980
41
102
saving interval
float32
count
12
Amount of saved intervals since
the measurement's start
Event count System 1 (U1..U4, I1,..,I4)
42
104
Trigger events
float32
count
2
43
106
Signal frequency trigger
float32
count
0
44
108
Voltage dips
float32
count
0
45
110
Voltage outages
float32
count
0
Event count System 2 (U5..U8)
46
112
Trigger events
float32
count
0
47
114
Signal frequency trigger
float32
count
0
48
116
Voltage dips
float32
count
0
49
118
Voltage outages
float32
count
Measurement channel averaging duration 1 s
50
120
U L1 rms
float32
V
229.1
51
122
U L2 rms
float32
V
230.2
52
124
U L3 rms
float32
V
228.4
53
126
U L4 rms / U NE
float32
V
3.4
54
128
U L12 rms
float32
V
389.5
55
130
U L23 rms
float32
V
390.1
56
132
U L31 rms
float32
V
388.8
57
134
U L1 Phase
float32
°
12.3
58
136
U L2 Phase
float32
°
132.3
59
138
U L3 Phase
float32
°
107.7