152
SICAM Q80 7KG8080
Power Quality Recorder SICAM Q80 7KG8080, System manual
E50417-H1076-C420-A2, Release 12.01.2015
5.1.8
Client-Server configuration
When there are multiple measurement devices and different workstations, it is possible to construct a variety of
architectures.
Server (main computer)
Must always stay in active state
Retrieves the data from all measurement devices
Import and analysis of the data
Measurement configuration
Client-PC
Graphical output of the measurement and results evaluation
Measurement configuration
Notes
As the number of users increases, the display refresh rate decreases.
Data import and extending the interval of data which were
just
displayed is NOT possible!
For this reason, import of data should be scheduled for times while no other work is being
performed. If data are being imported while analysis is running on the same PC, a warning
notification may be displayed.
Close the software upon receiving this notification. Alternatively, switch to a view without any
measured data and delete the software using the menu command
“Evaluation \ Delete
measurement data \ all open data”
.
Neither displayed measured data nor tables are automatically expanded as new data are
accumulated.
5.1.8.1
Setting up Client-Server operation
Server PC:
Measurement data folder: D:/SICAMQ80/Data/..
Database folder:
D:/SICAMQ80/DB/..
Share the folder: "D:/SICAMQ80/" as "SICAMQ80_ALL"
Example: Database entry for the measurement "Test_1" on 2/1/2012
Topology: Berlin/Station_1/ST_230V/Room_1/
Database entry
Start
2/1/2012 12:00 AM
End
2/2/2012 12:00 AM
Root folder
D:/SICAMQ80/Data
Subfolder
Room_1/Test_1/2012-02-01 00_00_00
Frequency
Freq.dat
For display of the frequency, the file "Freq.dat" is opened from the path "D:/SICAMQ80/Data/ Room_1/Test_1/2012-
02-01 00_00_00".