95
Operation modes and settings
Power Quality Recorder SICAM Q80 7KG8080, System manual
E50417-H1076-C420-A2, Release 12.01.2015
Holding Register addresses 51 through 59: General measurement status
No.
Register-
offset
Content
Format
Unit
Sample value
Value range
24
52
Synchronization flags
int32
-
Bit 1=1-Daylight Savings
Time /0=always UTC
Bit 2=1=measurement start time
determined/0-time switch still possible
Bit 3=1 - device uses Standard time
Bit 4=1 - device uses DST
Bit 5=1 - device unable to make time
switch/ 0- device running in valid UTC
or DST
Bit 6= Synchronization achieved only
after start of measurement -> device
time not synchronized (deviation from
correct time remains unchanged due to
Syncsignal)
Bit 7=1 since last start at least one
measurement was unsynchronized.
Bit 8=current measurement was
asynchronous at least once
25
54
SyncStatus
int16
-
0=not available
1=no synchronization signal available
2=valid synchronization signal
available, synchronization running
3=valid synchronization signal (DCF)
available, synchronization running
4=valid synchronization signal (GPS)
available, synchronization running
5=synchronized
6=synchronized (DCF)
7=synchronized (GPS)
8=valid synchronization signal (IRIG B)
available, synchronization running
9=synchronized (IRIG B)
10 =valid synchronization signal (NTP)
available, synchronization running
11=synchronized (NTP)
26
55
Time Zones Offset
int16
min
-720..720
27
56
Measurement status 1
int16
-
0 = Parameter loaded
1 = Measurement active
2 = Measurement concluded
3 = Error
28
57
Measurement status 2
int16
-
0 = All OK
1 = Phases interchanged
2 = L1 not connected
3 = L2 not connected
4 = L3 not connected
5 = parameters loaded, waiting for start
6 = All OK
7 = no measurement (concluded)
8 = waiting for timer start
29
58
DiskError
int16
-
Value is reset automatically after being
read!
30
59
OnlineError
int16
-
Value is reset automatically after being
read!