Startup
7.2 Applying the supply voltage
SENTRON PAC3200
92
Manual, 02/2008, A5E01168664B-04
7.2
Applying the supply voltage
A supply voltage is required to operate the device. Please consult the technical data or the
type plate for the type and level of the possible supply voltage.
CAUTION
Observe limit values
Failure to do so may result in damage to the device and the equipment.
The limits given in the technical data and on the type plate must not be exceeded even at
startup or when testing the device.
If a supply voltage is applied that does not comply with the specifications on the type plate,
this can result in malfunctioning and failure of the device.
The SENTRON PAC3200 can be supplied with an AC / DC multi-range power supply or a
DC extra-low voltage power supply.
Secure the supply voltage with an approved (UL / IEC) fuse appropriate to the power
supply version:
•
SENTRON PAC3200 with multi-range power supply 0.6 A, Type C.
•
SENTRON PAC3200 with extra-low voltage power supply 1.0 A, Type C.
If a fusible link is used, a suitable approved (UL / IEC) fuse holder has to be used. In
addition, a suitable isolating device shall be connected upstream in order to permit
disconnection of the device from the power supply.
The supply voltage must not be picked off at the voltage transformers.
Procedure
Connect the supply voltage to terminals L/+ and N/-.
Table 7-1
Connection of supply voltage
Terminal marking
Connection
L/+
AC: Connection: Conductor (phase-to-neutral voltage)
DC: Connection: +
N/-
AC: Connection: Neutral conductor
DC: Connection: -
See also
Applying the measuring voltage (Page 100)
Safety notes (Page 73)
Safety notes (Page 17)
Summary of Contents for SENTRON PAC3200
Page 16: ...Introduction 1 6 Further documentation SENTRON PAC3200 16 Manual 02 2008 A5E01168664B 04 ...
Page 90: ...Connection 6 4 Connection examples SENTRON PAC3200 90 Manual 02 2008 A5E01168664B 04 ...
Page 124: ...Operator control 8 2 Operator input steps SENTRON PAC3200 124 Manual 02 2008 A5E01168664B 04 ...
Page 125: ...Operator control 8 2 Operator input steps SENTRON PAC3200 Manual 02 2008 A5E01168664B 04 125 ...
Page 126: ......
Page 178: ...Glossary SENTRON PAC3200 178 Manual 02 2008 A5E01168664B 04 ...
Page 182: ...Index SENTRON PAC3200 182 Manual 02 2008 A5E01168664B 04 ...