Description
3.9 Ethernet port
SENTRON PAC3200
40
Manual, 02/2008, A5E01168664B-04
3.9.3
Modbus measured variables with the function codes 0x03 and 0x04
Measured variables of the SENTRON PAC Power Monitoring Device
The measured variables are provided by the SENTRON PAC Power Monitoring Device. You
can use the MODBUS function codes 0x03 and 0x04 on all the measured variables listed
below.
NOTICE
Error in the case of inconsistent access to measured values
Please ensure the start offset of the register is correct when making read accesses.
Please ensure the start offset and the number of registers are correct when making write
accesses.
If a value consists of two registers, a read command applied in the second register, for
example, will generate an error code. SENTRON PAC will also output an error code if, for
example, a write operation ends in the middle of a multi-register value.
Table 3-6
Available measured variables
Offset
Number of
registers
Name
Format
Unit
Value range
Access
1
2
Voltage V
a-n
Float
V
-
R
3
2
Voltage V
b-n
Float
V
-
R
5
2
Voltage V
c-n
Float
V
-
R
7
2
Voltage V
a-b
Float
V
-
R
9
2
Voltage V
b-c
Float
V
-
R
11
2
Voltage V
c-a
Float
V
-
R
13
2
Current a
Float
A
-
R
15
2
Current b
Float
A
-
R
17
2
Current c
Float
A
-
R
19
2
Apparent Power a
Float
VA
-
R
21
2
Apparent Power b
Float
VA
-
R
23
2
Apparent Power c
Float
VA
-
R
25
2
Active Power a
Float
W
-
R
27
2
Active Power b
Float
W
-
R
29
2
Active Power c
Float
W
-
R
31
2
Reactive Power a
Float
var
-
R
33
2
Reactive Power b
Float
var
-
R
35
2
Reactive Power c
Float
var
-
R
37
2
Power Factor a
Float
-
0 ... 1
R
39
2
Power Factor b
Float
-
0 ... 1
R
41
2
Power Factor c
Float
-
0 ... 1
R
43
2
THD-R Voltage a
Float
%
0 ... 100
R
45
2
THD-R Voltage b
Float
%
0 ... 100
R
Summary of Contents for SENTRON PAC3200
Page 16: ...Introduction 1 6 Further documentation SENTRON PAC3200 16 Manual 02 2008 A5E01168664B 04 ...
Page 90: ...Connection 6 4 Connection examples SENTRON PAC3200 90 Manual 02 2008 A5E01168664B 04 ...
Page 124: ...Operator control 8 2 Operator input steps SENTRON PAC3200 124 Manual 02 2008 A5E01168664B 04 ...
Page 125: ...Operator control 8 2 Operator input steps SENTRON PAC3200 Manual 02 2008 A5E01168664B 04 125 ...
Page 126: ......
Page 178: ...Glossary SENTRON PAC3200 178 Manual 02 2008 A5E01168664B 04 ...
Page 182: ...Index SENTRON PAC3200 182 Manual 02 2008 A5E01168664B 04 ...