3.9.7
Modbus status parameters with the function code 0x02
Status parameters
You can use the MODBUS function code 0x02 on all the status parameters listed below.
Table 3-10 Status parameters
Offset
Number of
registers
Name
Format
Value range
Access
0
0
Limit 0 status
Bit
R
1
0
Limit 1 status
Bit
R
2
0
Limit 2 status
Bit
R
3
0
Limit 3 status
Bit
R
4
0
Limit 4 status
Bit
R
5
0
Limit 5 status
Bit
0 =
No limit violation
1 =
Limit violation
R
50
0
Limit Logic status
Bit
R
108
0
Relevant parameter changes
Bit
R
109
0
Upper or lower limit violation
Bit
R
110
0
Maximum pulse rate exceeded
Bit
R
111
0
Restart of the device
Bit
R
112
0
Resetting of energy counter by user
Bit
R
116
0
Module slot 1
Bit
R
117
0
Maximum pulse rate exceeded
Bit
R
124
0
No synchronization pulse
Bit
R
125
0
Device Configuration menu is active
Bit
R
126
0
Voltage overload
Bit
R
127
0
Current overload
Bit
R
200
0
Digital input 0
Bit
R
300
0
Digital output 0
Bit
0 =
Not active
1 =
active
R
See also
Modbus measured variables with the function codes 0x03 and 0x04 (Page 40)
Summary of Contents for SENTRON PAC3200
Page 16: ...Introduction 1 6 Further documentation SENTRON PAC3200 16 Manual 02 2008 A5E01168664B 04 ...
Page 90: ...Connection 6 4 Connection examples SENTRON PAC3200 90 Manual 02 2008 A5E01168664B 04 ...
Page 124: ...Operator control 8 2 Operator input steps SENTRON PAC3200 124 Manual 02 2008 A5E01168664B 04 ...
Page 125: ...Operator control 8 2 Operator input steps SENTRON PAC3200 Manual 02 2008 A5E01168664B 04 125 ...
Page 126: ......
Page 178: ...Glossary SENTRON PAC3200 178 Manual 02 2008 A5E01168664B 04 ...
Page 182: ...Index SENTRON PAC3200 182 Manual 02 2008 A5E01168664B 04 ...