Parameterize
9.2 Parameterizing the operator interface
SENTRON PAC3200
134
Manual, 02/2008, A5E01168664B-04
Use PTs?
Measurement with/without voltage transformer
ON/OFF switch: ON / OFF.
ON: Measurement using voltage transformers.
When measuring via voltage transformer, the device
must know the voltage conversion ratio. For this
purpose, the primary and secondary voltages must be
specified in the fields "PT PRIMARY" and "PT
SECONDARY".
When changing from direct measurement to
measurement using voltage transformers, the device
accepts the last set reference measuring voltage as the
secondary voltage and as the primary voltage.
OFF: Measurement direct on the low-voltage
system.
When changing from measurement using voltage
transformers to direct measurement, the device
accepts the last set secondary voltage as the reference
measuring voltage.
Default: Off
VOLTAGE INPUT
Rated voltage of the measuring system. Must be specified if
measuring is done direct on the system without voltage
transformers.
SENTRON PAC3200 with multi-range power supply
Range: 1 V to 690 V, freely adjustable (max. 600 V for
UL)
Default value: 400 V
SENTRON PAC3200 with extra-low voltage power
supply
Range: 1 V to 500 V, freely adjustable
Default value: 289 V
The property "VOLTAGE INPUT" is only visible, if
"USE PTs?" is set to " Off".
PT PRIMARY
Primary voltage. Must be specified if a voltage transformer is
used for measuring.
Range: 1 V to 999999 V, freely adjustable
Default value: 400 V
The property "PT PRIMARY" is only visible, if
"USE PTs?" is set to " On".
Summary of Contents for SENTRON PAC3200
Page 16: ...Introduction 1 6 Further documentation SENTRON PAC3200 16 Manual 02 2008 A5E01168664B 04 ...
Page 90: ...Connection 6 4 Connection examples SENTRON PAC3200 90 Manual 02 2008 A5E01168664B 04 ...
Page 124: ...Operator control 8 2 Operator input steps SENTRON PAC3200 124 Manual 02 2008 A5E01168664B 04 ...
Page 125: ...Operator control 8 2 Operator input steps SENTRON PAC3200 Manual 02 2008 A5E01168664B 04 125 ...
Page 126: ......
Page 178: ...Glossary SENTRON PAC3200 178 Manual 02 2008 A5E01168664B 04 ...
Page 182: ...Index SENTRON PAC3200 182 Manual 02 2008 A5E01168664B 04 ...