Description
3.1 Features
SENTRON PAC3200
20
Manual, 02/2008, A5E01168664B-04
Device versions
The device is available in the following versions:
Table 3-1
Device versions
SENTRON PAC3200 Power Monitoring Device
Order No.
Description
7KM2112-0BA00-2AA0
SENTRON PAC3200 with multi-range power supply with ring lug terminals
7KM2112-0BA00-3AA0
SENTRON PAC3200 with multi-range power supply with screw terminals
7KM2111-1BA00-3AA0
SENTRON PAC3200 with extra-low voltage power supply with screw terminals
Measurement
●
Derivation of more than 50 measured variables from the basic measured variables with
maximum and minimum values (slave pointer function), as well as mean values for
phase-to-neutral voltages, phase-to-phase voltages and currents. The minimum and
maximum values are indicated in addition to the mean values.
●
With the multi-range power supply, the SENTRON PAC3200 can be connected direct to
690 V (max. 600 V for UL) industrial systems (measuring category III, pollution degree 2).
Higher voltages using voltage transformers.
●
With the extra-low voltage power supply, the SENTRON PAC3200 can be connected
direct to systems up to 500 V.
●
For current transformers x/1 A and x/5 A. Conversion ratio and current direction
programmable.
●
Can be used in 2-, 3- and 4-wire systems. Suitable for TN, TT and IT systems.
●
High measuring accuracy: 0.5% of the measured value for energy.
Counters and power demand
●
A total of 10 energy counters capture active energy, reactive energy, apparent energy for
off-peak and on-peak, import and export.
●
Calculation and storage of the last demand period mean value for active power and
reactive power for simple generation of load profiles using software. Programmable
demand period from 1 to 60 mins.
●
Configurable universal counter for counting limit violations and status changes at the
digital input or output, or for indicating the active power or reactive power of a connected
pulse encoder, e.g. S0 interface.
●
Working hours counter for monitoring the runtime of a connected load.
Summary of Contents for SENTRON PAC3200
Page 16: ...Introduction 1 6 Further documentation SENTRON PAC3200 16 Manual 02 2008 A5E01168664B 04 ...
Page 90: ...Connection 6 4 Connection examples SENTRON PAC3200 90 Manual 02 2008 A5E01168664B 04 ...
Page 124: ...Operator control 8 2 Operator input steps SENTRON PAC3200 124 Manual 02 2008 A5E01168664B 04 ...
Page 125: ...Operator control 8 2 Operator input steps SENTRON PAC3200 Manual 02 2008 A5E01168664B 04 125 ...
Page 126: ......
Page 178: ...Glossary SENTRON PAC3200 178 Manual 02 2008 A5E01168664B 04 ...
Page 182: ...Index SENTRON PAC3200 182 Manual 02 2008 A5E01168664B 04 ...