Technical data
11.1 Technical data
SENTRON PAC3200
160
Manual, 02/2008, A5E01168664B-04
Retention of data in the absence of the supply voltage
Measured values and counters are monitored for minimum and maximum values at specific
intervals and only saved to the non-volatile memory in the event of a change.
This means the age of the data before the power failure is as follows:
●
Minimum and maximum values max. 5 s
●
Counters max. 5 min
Connection elements
Measuring inputs and supply voltage
Screw-type terminals
Connection designations
IL1(°↑k, l↓), IL2(°↑k, l↓), IL3(°↑k, l↓)
V
1
, V
2
, V
3
, V
N
, L/+, N/-
1-wire or 2-wire connection possible
Solid
1 x 0.5 ... 4,0 mm²
AWG 1 x 20 ... 12
2 x 0.5 ... 2,5 mm²
AWG 2 x 20 ... 14
Finely stranded with end sleeve
1 x 0.5 ... 2,5 mm²
AWG 1 x 20 ... 14
2 x 0.5 ... 1.5 mm²
AWG 2 x 20 ... 16
Stripping length
10 mm
Connection screws
Tightening torque
0.8 ... 1.2 Nm
7 ... 10.3 lbf·in
Tool
Screwdriver PZ2
cal. ISO 6789
Crimping tool in accordance with EN 60947-1
Summary of Contents for SENTRON PAC3200
Page 16: ...Introduction 1 6 Further documentation SENTRON PAC3200 16 Manual 02 2008 A5E01168664B 04 ...
Page 90: ...Connection 6 4 Connection examples SENTRON PAC3200 90 Manual 02 2008 A5E01168664B 04 ...
Page 124: ...Operator control 8 2 Operator input steps SENTRON PAC3200 124 Manual 02 2008 A5E01168664B 04 ...
Page 125: ...Operator control 8 2 Operator input steps SENTRON PAC3200 Manual 02 2008 A5E01168664B 04 125 ...
Page 126: ......
Page 178: ...Glossary SENTRON PAC3200 178 Manual 02 2008 A5E01168664B 04 ...
Page 182: ...Index SENTRON PAC3200 182 Manual 02 2008 A5E01168664B 04 ...