Description
3.9 Ethernet port
SENTRON PAC3200
Manual, 02/2008, A5E01168664B-04
55
Table 3-20 Settings parameter for limit value 4
Offset
Number of
registers
Name
Unit
Format
Value range
Access
0 = OFF
50119
2
ON/OFF
-
unsigned long
1 =
ON
RW
50121
2
Hysteresis
%
float
0.0 ... 20.0
RW
50123
2
Delay
s
unsigned long
0 ... 10
RW
0 =
not used
1 =
AND
50125
2
Operation in Limit Logic
-
unsigned long
2 =
OR
RW
0 =
V_L1
1 =
V_L2
2 =
V_L3
3 =
V_L12
4 =
V_L23
5 =
V_L31
6 =
I_L1
7 =
I_L2
8 =
I_L3
9 =
VA_L1
10 = VA_L2
11 = VA_L3
12 = P_L1
13 = P_L2
14 = P_L3
15 = VAR_L1
16 = VAR_L2
17 = VAR_L3
18 = PF_L1
19 = PF_L2
20 = PF_L3
21 = THDV_L1
22 = THDV_L2
23 = THDV_L3
24 = THDI_L1
25 = THDI_L2
26 = THDI_L3
27 = FREQ
28 = V_LN_AVG
29 = V_LL_AVG
50127
2
Source
-
unsigned long
30 = I_AVG
RW
Summary of Contents for SENTRON PAC3200
Page 16: ...Introduction 1 6 Further documentation SENTRON PAC3200 16 Manual 02 2008 A5E01168664B 04 ...
Page 90: ...Connection 6 4 Connection examples SENTRON PAC3200 90 Manual 02 2008 A5E01168664B 04 ...
Page 124: ...Operator control 8 2 Operator input steps SENTRON PAC3200 124 Manual 02 2008 A5E01168664B 04 ...
Page 125: ...Operator control 8 2 Operator input steps SENTRON PAC3200 Manual 02 2008 A5E01168664B 04 125 ...
Page 126: ......
Page 178: ...Glossary SENTRON PAC3200 178 Manual 02 2008 A5E01168664B 04 ...
Page 182: ...Index SENTRON PAC3200 182 Manual 02 2008 A5E01168664B 04 ...