Technical data
11.1 Technical data
SENTRON PAC3200
Manual, 02/2008, A5E01168664B-04
159
Digital output
Number
1 output
External power supply
12 to 24 V DC
Max. switched output voltage
30 V DC
Output current
For signal "1"
10 to 27 mA
Continuous load
max. 100 mA
Transient overload
max. 300 mA for a duration of 100 ms
Resistive load
100 mA
For signal "0"
max. 0.2 mA
Switch rate
17 Hz
Short-circuit protection
Yes
Power supply
Table 11-1 AC/DC multi-range power supply
Rated range
95 … 240 V AC (50/60 Hz) or
110 … 340 V DC
Work area
± 10% of AC rated range
± 10% of DC rated range
Power consumption
Typically 8 VA (with optional expansion module).
Overvoltage category
CAT III
Table 11-2 Extra-low voltage DC power supply:
Rated range
24 V, 48 V and 60 V DC or
22 to 65 V DC
Work area
± 10% of rated range DC
Power consumption
Typically 8 VA (with optional expansion module).
Overvoltage category
CAT III