3.9 Ethernet port
SENTRON PAC3200
Manual, 02/2008, A5E01168664B-04
61
3.9.11
Modbus command parameters
Addressing the command parameters
You can use MODBUS function code 0x06 on the command parameters.
Table 3-26 Command parameters
Offset
Number
of
registers
Name
Unit
Format
Value range from ... to
Access
60002
1
Reset maximum values
-
unsigned short
0
W
60003
1
Reset minimum values
-
unsigned short
0
W
0 =
All
1 =
Active Energy
Import Tariff 1
2 =
Active Energy
Import Tariff 2
3 =
Active Energy
Export Tariff 1
4 =
Active Energy
Export Tariff 2
5 =
Reactive Energy
Import Tariff 1
6 =
Reactive Energy
Import Tariff 2
7 =
Reactive Energy
Export Tariff 1
8 =
Reactive Energy
Export Tariff 2
9 =
Apparent
Energy Tariff 1
60004
1
Reset energy counter
-
unsigned short
10 =
Apparent
Energy Tariff 2
W
60005
1
Synchronization of the
demand period
Min.
unsigned short
1 ... 60
W
0 =
High tariff
60006
1
Switching tariff
-
unsigned short
1 =
Low tariff
W
60007
1
Acknowledge the diagnostics
bit
1)
(cf. stored bits in
unsigned long beginning
offset 205)
-
unsigned short
0 ... ffffh
W
0 = output 0
OFF
60008
1
Switching outputs (if
parameterized)
-
unsigned short
1 = output 0
ON
W
Summary of Contents for SENTRON PAC3200
Page 16: ...Introduction 1 6 Further documentation SENTRON PAC3200 16 Manual 02 2008 A5E01168664B 04 ...
Page 90: ...Connection 6 4 Connection examples SENTRON PAC3200 90 Manual 02 2008 A5E01168664B 04 ...
Page 124: ...Operator control 8 2 Operator input steps SENTRON PAC3200 124 Manual 02 2008 A5E01168664B 04 ...
Page 125: ...Operator control 8 2 Operator input steps SENTRON PAC3200 Manual 02 2008 A5E01168664B 04 125 ...
Page 126: ......
Page 178: ...Glossary SENTRON PAC3200 178 Manual 02 2008 A5E01168664B 04 ...
Page 182: ...Index SENTRON PAC3200 182 Manual 02 2008 A5E01168664B 04 ...