SENTRON PAC3200
Manual, 02/2008, A5E01168664B-04
65
Operation planning
4
4.1
Operation planning
Mounting location
The SENTRON PAC3200 device is intended for installation in permanently installed
switching panels within closed rooms.
Conductive panels and doors on control cabinets must be grounded. The doors of the control
cabinet must be connected to the control cabinet using a grounding cable.
Mounting position
The device must be installed vertically.
r
r
Figure 4-1
Mounting position
The preferred viewing angle is 6 o'clock (bottom view).