Description
3.9 Ethernet port
SENTRON PAC3200
Manual, 02/2008, A5E01168664B-04
59
3.9.10
Modbus device information with the function codes 0x03, 0x04 and 0x10
Addressing the device information parameters
You access the following device information parameters block-by-block only, e.g. read from
Offset 64001 27 Register.
NOTICE
Error in the case of inconsistent access to I&M data
Please ensure the start offset and the number of registers are correct when making read
accesses and write accesses. Always read or write the entire block.
Please ensure the start offset and the number of registers are correct when making write
accesses.
If a value consists of several registers, a read command applied in the second register, for
example, will generate an error code. SENTRON PAC will also output an error code if, for
example, a write operation ends in the middle of a multi-register value.
Table 3-23 I&M 0 parameter of the SENTRON PAC Power Monitoring Device with the function codes 0x03 and 0x04
Offset
Total
registers
Number of
registers per
parameter
Name
Format
Value range
from ... to
Access
Start offset
64001
[1]
Manufacturer's ID
unsigned short
0 ... 65535
Standard: 42
*)
R
[64002]
[10]
Order No.
Char 20
ASCII
R
[64012]
[8]
Serial number
Char 16
ASCII
R
[64020]
[1]
Hardware version
unsigned short
0 ... 65535
R
[64021]
[2]
Firmware version
1 char, 3 unsigned
char
V 0.0.0 ...
V 255.255.255
R
[64023]
[1]
Counter for changes
unsigned short
1 ... 65535
R
[64024]
[1]
Profile ID
unsigned short
3A00 ... F6FF
R
[64025]
[1]
Specific Profile ID
unsigned short
-
R
[64026]
[1]
Version of the I&M data 2 unsigned char
0.0 ... 255.255
R
[64027]
27
[1]
Supported I&M data
unsigned short
00 ... FF
R
*) 42 stands for Siemens AG
Summary of Contents for SENTRON PAC3200
Page 16: ...Introduction 1 6 Further documentation SENTRON PAC3200 16 Manual 02 2008 A5E01168664B 04 ...
Page 90: ...Connection 6 4 Connection examples SENTRON PAC3200 90 Manual 02 2008 A5E01168664B 04 ...
Page 124: ...Operator control 8 2 Operator input steps SENTRON PAC3200 124 Manual 02 2008 A5E01168664B 04 ...
Page 125: ...Operator control 8 2 Operator input steps SENTRON PAC3200 Manual 02 2008 A5E01168664B 04 125 ...
Page 126: ......
Page 178: ...Glossary SENTRON PAC3200 178 Manual 02 2008 A5E01168664B 04 ...
Page 182: ...Index SENTRON PAC3200 182 Manual 02 2008 A5E01168664B 04 ...