Appendix
A.1 Modbus TCP
PAC2200CLP
Equipment Manual, 06/2021, L1V30820585B-02
97
Offset Number
of regis-
ters
Name
Format
Unit Value range
Access
555
2
Reactive energy export current period Float
varh -
R
557
2
Length of demand period (measure-
ment duration)
Unsigned long ms
-
R
559
2
Status information
Unsigned long
BYTE 0 0x00 TARIFF 1
BYTE 0 0x01 TARIFF 2
Bit 23: Measuring input
out of range
Bit 22: Power failure
Bit 21: Time inaccurate
Bit 16: Short period
Bit 18: Multi-
synchronization
Bit 12: New event in
logbook
Bit 6: Reactive power
type VAR1
Bit 0: Period is invalid
R
561
4
Active energy import current period T1 Double
Wh
-
R
565
4
Active energy import current period T2 Double
Wh
-
R
569
4
Reactive energy import current period
T1
Double
varh -
R
573
4
Reactive energy import current period
T2
Double
varh -
R
577
4
Active energy export current period T1 Double
Wh
-
R
581
4
Active energy export current period T2 Double
Wh
-
R
585
4
Reactive energy export current period
T1
Double
varh -
R
589
4
Reactive energy export current period
T2
Double
varh -
R
593
4
Active energy import current period
T1+T2
Double
Wh
-
R
597
4
Active energy export current period
T1+T2
Double
Wh
-
R
801
4
Active energy import tariff 1
Double
Wh
Overflow 1.0e+12
R
805
4
Active energy import tariff 2
Double
Wh
Overflow 1.0e+12
R
809
4
Active energy export tariff 1
Double
Wh
Overflow 1.0e+12
R
813
4
Active energy export tariff 2
Double
Wh
Overflow 1.0e+12
R
817
4
Reactive energy import tariff 1
Double
varh Overflow 1.0e+12
R
821
4
Reactive energy import tariff 2
Double
varh Overflow 1.0e+12
R
825
4
Reactive energy export tariff 1
Double
varh Overflow 1.0e+12
R
829
4
Reactive energy export tariff 2
Double
varh Overflow 1.0e+12
R
833
4
Apparent energy tariff 1
Double
VAh Overflow 1.0e+12
R
837
4
Apparent energy tariff 2
Double
VAh Overflow 1.0e+12
R
841
4
L1 active energy import tariff 1
Double
Wh
Overflow 1.0e+12
R
845
4
L1 active energy import tariff 2
Double
Wh
Overflow 1.0e+12
R
849
4
L1 active energy export tariff 1
Double
Wh
Overflow 1.0e+12
R
853
4
L1 active energy export tariff 2
Double
Wh
Overflow 1.0e+12
R
857
4
L1 reactive energy import tariff 1
Double
varh Overflow 1.0e+12
R
861
4
L1 reactive energy import tariff 2
Double
varh Overflow 1.0e+12
R
Summary of Contents for SENTRON PAC2200CLP
Page 1: ......
Page 2: ......
Page 8: ...Table of contents PAC2200CLP 6 Equipment Manual 06 2021 L1V30820585B 02 ...
Page 14: ...Introduction 1 6 Risk of manipulation PAC2200CLP 12 Equipment Manual 06 2021 L1V30820585B 02 ...
Page 78: ...Service and maintenance 7 4 Warranty PAC2200CLP 76 Equipment Manual 06 2021 L1V30820585B 02 ...
Page 129: ......
Page 130: ......