PAC2200CLP
Equipment Manual, 06/2021, L1V30820585B-02
77
Technical specifications
8
8.1
Technical specifications
Device configuration
•
1 optically isolated digital input
•
1 optically isolated digital output
•
1 Ethernet interface for connection to and configuring on the PC or network
Measurement
Only for connection to AC voltage systems
Measuring method
For voltage measurement
True root-mean-square measurement (TRMS)
For current measurement
True root-mean-square measurement (TRMS)
Measured value acquisition
Energy
Contiguous (zero blind measuring)
Current, voltage
Contiguous (zero blind measuring)
Waveform
Sinusoidal or distorted
Frequency of the relative fundamental
50 Hz
Measuring inputs for voltage (5 A/65 A devices)
Measuring inputs
Voltage U
n (L-N / L-L)
230 V / 400 V AC, 50 Hz
Max. measurable voltage
Voltage L-N
230 V 3AC (+20%)
Voltage L-L
400 V 3AC (+20%)
Min. measurable voltage
Voltage L-N
100 V 3AC (-80%)
Voltage L-L
173 V 3AC (-80%)
Zero point suppression level
Voltage L-N
7 V
Voltage L-L
10 V
Impulse withstand voltage
6.5 kV (1.2 / 50 µs)